Instructions

Technical specifications
Separator: 2”–4” ANSI 150 CLASS
2”–6” ANSI 150 CLASS (ASME)
Connections: - Air vent relief: 3/8” Female
- Drain valve: 1 1/4” NPT Female
Materials: - Separator body: Epoxy resin painted steel
- Air vent body: Brass
- Shut-off and drain valve body: Brass
- Int. element: Stainless steel
- Air vent seal: VITON
- Air vent float: Stainless steel
Medium: Water and non-hazardous glycol solutions up to 50%
Max operating pressure: 150 psi (10 bar)
Temperature range: 32–250°F (0–120°C)
Particle separation capacity: to 5 µm
Technical
specifications
of insulation
Inner part
Material: rigid closed cell expanded polyurethane foam
Thickness: 2 3/8” (60 mm)
Density: 3 lb/ft
3
(45 kg/m
3
)
Conductivity (ISO 2581): 0.16 BTU/in (0.023 W/(m·K)
Temperature range: 32–220°F (0–105°C)
Outer part
Material: Embossed aluminium
Thickness: 7-mil (0.70 mm)
Fire resistance (DIN 4102): Class 1
Head covers
Heat formed material: PS
CAUTION: Make sure that all the connecting pipework is water tight.
CAUTION: When making the water connections, make sure that the
hydronic separator connecting pipework is not mechanically over-
stressed. Over time this could cause breakages, with consequent water
losses which, in turn, could cause harm to property and/or people.
CAUTION: Water temperatures higher than 100°F (38°C) can be
dangerous. During the installation, commissioning and maintenance of the
hydronic separator, take the necessary precautions to ensure that such
temperatures do not endanger people.