Product Overview
Maintenance
To perform maintenance after isolating
the separator, simply unscrew the
top cover using the provided key and
remove the attached internal element
inside the collection chamber.
This multifunction device can also be used as a dosing point to inject
chemical additives into the circuit. Codes NA545355 and NA545356
offer integral isolation check valves making for a more convenient dosing
vessal, providing an easy access point for routine system water treatment
in hydronic systems.
Use a screwdriver to undo the screw on the top plug in order to purge any
air that has collected at the top of the body.
Dosing
Installation
The magnetic dirt separator should be installed in accordance with the
flow direction indicated by the arrow on the tee fitting and the return
circuit upstream of the boiler. The magnetic dirt separator should
always be installed upstream of the pump and always with its body
in vertical position.
1 2
Draining off dirt and ferrous impurities
Remove the magnetic ring (1) and drain the collected dirt and ferrous
impurities. This can be done while the system is running, using the
key provided (2).
Air vent
Eliminate air collected in the
top of the body by loosening
the top plug screw.