Solar Thermal Information
63
Characteristics
Pump speed control functions (iSolar 2, 4 & Plus)
Pump speed control can improve system efficiency by reducing
the flow to the collectors on cloudy days to improve solar thermal
transfer and reduce electrical consumption. This is achieved
by the differential temperature value between the collectors
and storage tank.
If the value for the ΔT switch-on is reached (e.g. ΔT on = 9º),
the pump will start with 100% pump speed for 10 seconds, then
reduce the speed to the adjusted minimum pump speed (min.
pump speed = 30 %, adjustable). If the temp-erature difference
reaches the set value (e.g. ΔT Set = 18º), pump speed will in-
crease by 10 %. At any further rise of 3º ΔT the pump speed will
increase by 10% until the maximum of 100% is reached.
+
– +
SET
!
ê
?
?
F
R
User-friendly operation
System screen LCD display
with 16-segment display and
8 symbols for system status
Operating LED control lamp
3 push-button controls
Attractive design and
compact dimensions
Easy to install
Standard operation functions
iSolar
120V 120V 120V 120V 120V
12 or 24V
1 iSolar 2 iSolar 3 iSolar Plus
Standard relay output 102 0
Speed control triac output (30 to 100%) 0 1 0 2
Sensor inputs (temperature)
Max. solar collector arrays
Max. solar storage tanks
Two tank priority logic
Heat dump function (second relay)
A062752A032752A022752A012752Code
Selectable programs 1 1 3
iSolar 4
1
1
Drainback pump speed control
Drainback booster pump (second relay)
Thermostat function (second relay)
Backup heat function (second relay)
yes
A042752
3 10
iSolar Plus PV
2
0
444 444
111 212
111 212
no no no no yes
yesno no no no yes
yesyesyesno no yes
yesyesyesno no yes
yesyesyesno no yes
yesyesyesno no yes
yesyesyesno no yes
yesyesyesyesyes yes
yesyesyesyesyes yes
yesyesyesyesyes yes
yesyesyesyesyes yes
yesyesyesyesyes yes
yesyesyesyesyes yes
yesyesyesyesyes yes
yesyesyesyesyes yes
yesyesyesyesyes yes
yesno no noyesyes
257260A
PV1 or PV2
10
Second deltaT-function
Real time clock (timer function)
Collector freeze protection
Evacuated tube collector function
Min. collector temperature
Vbus data commincation
Tank (night time) cooling
Emergency shutdown functions
Operating hours counter
Energy metering measurement
Collector cooling functions