Solar Thermal Information

12
combination with a mixing device to regulate the temperature
of the supply air stream. Such regulation prevents very hot
water in the solar storage tank from creating a burst of very
warm air to the heated space.
The size of the plenum coil should allow relatively low water
temperatures in the solar storage tank to meet the heating load.
Coils with multiple tubing rows and large aluminum fins improve
heat transfer at low water temperatures, and as such are preferred.
Coil manufacturers can size coils for the required rates of heat
transfer at specified entering water and air temperatures.
This type of system may not always create supply air
temperatures as high as those created by a furnace, especially
if the water temperature supplied to the coil is regulated by
outdoor reset control. The registers and diffusers used for
such a system should be carefully sized and placed to avoid
creating drafts within the heated space. Ideally, supply air
from the diffusers should be mixed with room air above the
occupied zone. Vertical air velocities into the occupied zones
should be minimized to avoid drafts.
Fin-tube baseboards, although commonly used in conventional
hydronic systems, generally do not provide good performance
duct coil
(in plenum)
blower
filter
furnace
return air
to/from
solar storage
tank
supply air
burners off
when heated
water is supplied
from solar
subsystem
mixing valve
check valve
supply air temperature sensor
figure 3-10
figure 3-11