Brochure

12131218
68
Balancing valve with flow meter.
Direct reading of flow rate.
No sight gauge clouding or scaling.
Brass valve body and flow meter.
Rotatable valve for flow rate adjustment.
Graduated scale flow meter with magnetic
movement flow rate indicator.
6HSGHMRTK@SHNM
Max. working pressure: 150 psi.
Temperature range: 14—230°F.
Max. percentage of glycol: 50%.
132
QuickSetter
tech. broch. 01149
Code Description Flow scale (gpm) Pk Lbs USD
132432A ½" NPT 0.5—1.75 1 2.0 241.00
132552A ¾" NPT 2.0—7.0 1 1.8 259.60
132662A 1" NPT 3.0—10.0 1 2.4 302.80
132772A 1¼" NPT 5.0—19.0 1 2.8 401.60
132882A 1½" NPT 8.0—32.0 1 3.4 475.80
132992A 2" NPT 12.0—50.0 1 4.4 584.20
F19346 Replacement by-pass valve stem* 1 0.1 48.80
* With operating ring.
%KNVQ@SD@CITRSLDMS
The flow rate is adjusted as follows:
"NLOKDSDNODMHMF@MCBKNRHMFNESGDU@KUD
A. With the aid of the flow rate
indicator (1), mark the desired
flow rate.
B. Use the operating ring (2)
to open the by-pass valve
slowly. This allows fluid to flow
through the flow meter (3). The
bypass valve is automatically
closed under normal operating
conditions.
Full opening of the valve Full closing of the valve
C. While holding the bypass valve open, use a wrench to turn the valve
control stem (4) to adjust the flow rate slowly. The resulting flow rate
is indicated by the metal ball (5) that slides up and down inside a
transparent channel (6) marked by a graduated scale in gpm.
D. Once the flow rate is properly adjusted, release the operating ring (2)
of the by-pass valve. The valve will automatically return to the closed
position by means of an internal spring.
E. A replacement by-pass valve stem (7) with operating ring is available in
event it is damaged and inoperable. Order code F19346.
"NMRSQTBSHNMCDS@HKR
In the QuickSetter™ series the flow rate (gpm) is displayed directly by a flow
meter housed in a by-pass circuit on the valve body, which automatically is
shut-off during normal operation.
The flow meter permits fast and easy circuit balancing without need for
differential pressure gauges and reference charts.
! + -"(-&5 +5$6(3'%+.6,$3$1