Product Overview
Wiring diagrams
1. Connection diagram for room SPDT thermostat (RT) and
electric supply.
The illustrated connection permits opening and closing the valve
according to the ambient thermostat signal.
2. Connection diagram for single contact thermostat (RT) or
on-off switching device.
If the termostat has only a single contact, or on-off switch is used,
install a SPDT relay as shown below.
M
CLOSE
OPEN
RT
N
L
Max
5 A
ACTUAT OR
M
CLOSE
OPEN
RT
N
L
Max
5 A
ACTUAT OR
M
CLOSE
OPEN
RT
N
L
Max
5 A
ACTUAT OR
M
CLOSE
OPEN
RT
N
L
Max
5 A
ACTUAT OR
Auxiliary micro-switches
The motor is equipped with limit micro-switches that shut off the
motor when reaching the valve open/closed positions.
The auxiliary micro-switch turns on average at 80% valve opening.
3. Pump disconnection diagram when no zone is in operation.
This diagram, using the auxiliary micro-switch,
turns off the pump
when the zone valve is closed.
If the pump has an input current greater than 5 A (24 V), use an
intermediate relay.
M
CLOSE
OPEN
24 VAC
Relay
N
L
Max
5 A
ACTUATOR
RT