User Guide
Installations
To install the flow switch correctly follow these instructions:
-Select the blade marked with the diameter of the pipe in which the
switch is to be installed;
-Remove any extra pre-fitted blades for larger diameter pipes by
unscrewing the 2 blade attaching screws;
-With pipe diameters of 3” (DN 80) or above, all the pre-fitted blades
must be attached in ascending order with the long blade being cut
to the size corresponding to the desired pipe diameter;
-Fit the flow switch to the pipe, carefully observing the direction of
flow indicated by the arrows stamped on the cover and on the switch
mounting plate. When fitted, the distance between the upper surface
of the pipe and upper surface of the switch mounting plate should
be 3 1/8” (80 mm);
-The tee connection in the pipe can be formed by the direct welding
of a threaded socket;
-This also applies to a 1” (DN 25) diameter pipe, as the blades are
designed to be contained in these smaller dimensions.
-It is however advisable to check that the weld is free from burrs on
the inside so that the blade can move freely in the tee connection;
-Whenever possible the flow switch should be installed in the
vertical
position to avoid deposits of impurities which may cause it to
function incorrectly.
CAUTION:
All work must be performed by qualified personnel trained in
the proper application, installation, and maintenance of systems in
accordance with all applicable codes and ordinances.
ATTENTION: Tous les travaux doivent être effectués par du personnel
qualifié formé à la bonne application, installation et maintenance des systèmes
conformément aux codes et règlements locaux.
CAUTION:
Over-tightening and breakage can occur with the use of PTFE
pipe joint compounds. PTFE provides lubricity so that care must be
exercised not to over-tighten joints. Failure to follow these instructions
could result in property damage and /or personal injury.
ATTENTION: Un serrage excessif et la rupture peuvent se produire avec l'utilisation
de raccords filetés de tuyaux téflon. Téflon fournit un pouvoir lubrifiant afin qu'il doit
être prudent pour ne pas trop serrer les joints. Suivre ces instructions peut entraîner.
WARNING:
Electrical shock hazard. Disconnect ALL power sources when
installing or servicing this equipment to prevent electrical shock or
equipment damage. Failure to follow these instructions could result in
property damage and/or personal injury.
ATTENTION: Risque d’électrocution. appareil sous tension. Coupez l’alimentation
électrique avant d’effectuer toute intervention. Le non respect de ces indications
peut provoquer des lésions corporelles ou des dégâts matériels.
3 1/8”
3/4”
1"
1
1
2"
2
8"-DN200
6"-DN150
5"-DN125
4"-DN100
3"-DN 80
DN175
WARNING: This product can expose you to chemicals including lead, which is
known to the State of California to cause cancer and birth defects or other
reproductive harm. For more information go to www.P65Warnings.ca.gov.
AVERTISSEMENT: Ce produit peut vous exposer à des produits chimiques
comme le plomb, qui est connu dans l’État de Californie pour causer le cancer,
dommages à la naissance ou autre. Pour plus d’informations rendez-vous
www.P65Warnings.ca.gov.