Brochure
01052/09 NA
Flow switch
series 626
Function
The flow switch detects whether there is any flow in the pipe and
opens or closes an electrical contact. It is normally used in heating,
air-conditioning, refrigeration, water treatment, additive pumping
and process systems in general. By means of the flow switch it is
possible: to control devices such as pumps, burners, compressors,
refrigerators,
motorized valves; to turn on indicator and alarm
devices and regulate equipment for dosing water additives.
In heating s
ystems, especially, the flow switch functions to switch
the burner off in case of a lack of medium circulation within the
water heater circuit. A lack of circulation would otherwise impair
the operation of the temperature-sensitive safety and protection
devices.
Product range
Code 626600A Flow switch Size 1” NPT
Code 626009 Replacement paddles (blades)
CALEFFI
Technical specifications
Materials
Body: brass
Cover: self-extinguishing polycarbonate
Microswitch protection casing: self-extinguishing polycarbonate
Bellows rod and bellows: stainless steel
Paddle (Blades) for pipes: stainless steel
Microswitch spring: stainless steel
O-Ring seals: EPDM
Performance
Medium: drinking water and glycol solutions
Max. percentage of glycol: 50%
Max. working pressure: 150 psi (10 bar)
Medium temperature range: -20–250°F (-30
–
120°C)
Max. ambient temperature: 130°F (55°C)
Connection: 1” NPT male
Pipe adjustability: from 1” to 8”
Electric specifications
Voltage: 250 V
Electrical connection: 1/2" FNPT threaded
Current: 15 (5) A
Protection class: NEMA Type 5 (IP 54 )
Certification: CE, C-UL
Dimensions
B
ED
C
A
A
1"
C
5
5/16”
B
3
7/16”
D
2 15/16”
E
2 3/8”
Code
626600A
Weight (lb)
2.05
30V9
U
L
®
C US
ACCREDITED
ISO 9001 No. 0003
ISO 9001 FM 21654