User Guide

Electrical Data
Max Voltage: 250 VAC
Current: 15 A
Electrical connection: 1/2” NPT threaded
Protection class: NEMA type 5 (IP54)
Certification Mark:
SAFETY INSTRUCTION
This safety alert symbol will be used in this manual to draw attention to
safety related instructions. When used, the safety alert symbol means
ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED!
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN
A SAFETY HAZARD.
CONSIGNE DE SÉCURITÉ
Ce symbole d'avertissement servira dans ce manuel à attirer l'attention sur la sécurité concernant
instructions. Lorsqu'il est utilisé, ce symbole signifie ATTENTION ! DEVENEZ ALERTE !
VOTRE SÉCURITÉ EST EN JEU ! NE PAS SUIVRE CES INSTRUCTIONS PEUT
PROVOQUER UN RISQUE DE SÉCURITÉ.
Function
The Caleffi Series 626 water flow switch detects the presence or absence
of flow in piping of heating, air conditioning, cooling and water treatment
systems as well as in pumping and process systems. In heating systems,
the flow switch is normally used to shut off the burner of the boiler whenever
there is no circulation of the carrier fluid in the boiler circuit. A lack of
circulation can damage criti
cal components and impair the operation of
temperature sensitive safety and protection devices.
Flow Switch
626 Series
68235.0
5
General Characteristics
A stainless steel bellows separates the electrical and hydronic sections, preventing the possibility
of contact of the fluid with the electrical components. Stainless steel is used in the construction of
many key parts, including the bellows, which protects the switch from corrosion.
With a protection classification of NEMA type 5 (IP54), the switch can be used in particularly
humid and dusty environments. The cover is made of a special non-combustible plastic material.
The normally open and normally closed contacts on the switch enable any electrical device to be
switched on or off as required at the operating flow rate. The operating point can be easily adjusted
with the calibration screw.
Technical Characteristics
Connection size: 1” NPT male
Maximum operating pressure: 150 psig (10 bar)
Maximum temperature of the fluid: 250° F (120°C)
Minimum temperature of the fluid: -20° F (-30°C)
Maximum ambient temperature: 130° F (55°C)