Install Instructions
5
Mixing valve performance
Accuracy: ± 3º F (± 2º C)
Max. operating differential pressure (dynamic): 20 psid (1.4 bar)
Max. ratio between inlet pressures (H/C or C/H): 2.1
5
Controller, LCD user interface/display
Materials: - Housing: self-extinguishing ABS, color white RAL 1467
- Cover: self-extinguising SAN, smoked transparent
Electric supply: 24 VAC (min 21.6, max 26.0 VAC)- 50/60 Hz
(115/24 VAC transformer included in package)
Power consumption: 6.0 VA
Adjustment temperature range: 70 - 185°F (20 - 85°C)
Disinfection temperature range: 100 - 185°F (40 - 85°C)
Ambient temperature range: 32 - 120°F (0 - 50°C)
Protection class: IP 54 (wall mounting)
(Class II appliance)
Mounting bracket: DIN rail
Mixing valve control: 1 A / 24 V
Alarm relay (R2): 5 (2) A / 24 V
Contact rating (R1, R3, R4): 10 (2) A / 24 V
Fuses: 1 (main): 400 mA
Fuses: 2 (mixing valve): 1 A
Charge reserve: 15 days in the event of electric supply failure,
with a 3 cell rechargeable 3.6 V 140 mAh buffer battery
Battery recharging time: 140 hours
Approvals: CE, FCC part 15
Temperature sensors
Body material: stainless steel
Type of sensitive element: NTC
Working temperature range: 14 - 260°F (-10 - 125° C)
Resistance: 10,000 Ohms at 77° F (25° C)
Time constant: 2.5
Max. distance for mixed outlet or return (recirculation) sensor:
500 ft (150 m) cable 2 conductor x AWG 18
800 ft (250 m) cable 2 conductor x AWG 16
Recommended Flow Rates (gpm/lpm)
Size ¾" 1" 1¼" 1½" 2" 2½" 3"
Minimum (1) 2.2 / 8.3 3.1 / 11.7 4.4 / 16.6 6.6 / 25 8.8 / 33.3 17.0 / 64 22.0 / 83.3
Design Flow (2) 27 / 102 58 / 220 66 / 250 93 / 352 131 / 495 288 / 1,090 329 / 1,245
Maximum (3) 43 / 172 94 / 356 107 / 405 152 / 575 215 / 814 470 / 1,780 537 / 2,033
Cv 9.7 21 24 34 47 105 120
(1) To ensure stable operation and a ± 3° F accurate temperature control. Minimum flow rate is 0 gpm when
recirculation flow rate is greater than or equal to the valve size minimum flow rating.
(2) Suggested maximum flow rate for optimum modulating control (at 7.5 psid pressure drop).
(3) Maximum recommended differential pressure is 20 psid to ensure stable operation and accurate temperature control.