Install Instructions

0x03 0x06
0 0000 Product type Code to dene the product 6001 x
1 0001 BUS address 1…247 x
2 0002 T mix (°C) x
3 0003 T rec (°C) x
4 0004 T mix (°F) x
5 0005 T rec (°F) x
6 0006 STATUS 0= - x
1= regulation
2= disinfection
3= ushing
4= thermal shock
5= alarm
7 0007 PROGRAM 0= Program 0 x x
1= Program 1A
2= Program 1B
3= Program 2
8 0008 DAY 1…31 x x
9 0009 MONTH 1…12 x x
10 000A YEAR 2017… x x
11 000B HOUR 0…23 x x
12 000C MINUTE 0…59 x x
13 000D LANGUAGE 0= IT x x
1= EN
2= FR
3= DE
4= ES
5= P
6= NL
7= SL
8= HR
9= SR
10= RO
14 000E TIME ON - h (Disinfection start hour) 0…23 x x
15 000F TIME ON - min (Disinfection start minute) 0…59 x x
16 0010 TIME OFF - h (Disinfection stop hour) 0…23 x x
17 0011 TIME OFF - min (Disinfection stop minute) 0…59 x x
18 0012 TIME wait (time read ing recirc. Temp.) 1…255 (min) x x
19 0013 TIME min (MINIMUM DISINFECTION TIME) 0…254 (min) x x
20 0014 TIME ux (after ending the disinfection) 0…2550 (sec) x x
21 0015 TIME shock (time of duration shock) 1…4320 (min) x x
22 0016 SET REG - mixing regulation set temperature 20…85 (°C) x x
23 0017 SET DIS - disinfection set temperature 40…85 (°C) x x
24 0018 SET REC - recirculation set temperature 40…85 (°C) x x
25 0019 SET SHOCK - shock set temperature 30…85 (°C) x x
26 001A SET Tmax - Maximum limit of range set temperature 50…90 (°C) x x
FUNCTION
VALUEREG (hex) DESCRIPTIONREG
4= Friday
5= Saturday
6= Sunday
33 0021 Active functions b0: Presence of recirc. probe x x
b1: Anticlog
b2:0 b3:0 = Legal hour OFF b2:1 b3:0 = Legal hour EU b2:0 b3:1 = Legal hour US b2:1 b3:1 = Legal hour CUST
-
b4: Internatiol System of Unit
b5: LED display enable
34 0022 Forced activities 0= Shock activation x
1= Pin-code reset
2= Disinfection reset
3= Alarm reset
4= Historical data reset
35 0023 TIME motor - from close to full open 8…320 (sec) x x
36 0024 TIME play - delay of time of actuator 1…255 (sec) x x
37 0025 START Sunday legal hour -3…3 x x
38 0026 START Month legal hour 1…12 x x
39 0027 END Sunday legal hour -3…3
x x
40 0028 END Month legal hour 1…12
x x
MODBUS functions:
Function 0x03 - Read Holding Registers
Used to read one or more parameters (the size of every parameter is 16 bit)
The frame has the following structure:
dev. Addr. func start addr H start addr L N.regs H N.regs L CRC16H CRC16L
HH 03 HH HH 00 HH HH HH
dev. Addr. – Address of the device on the RS485 net (1-247)
Func Function code = 3
start addr H - MSByte of the address of the parameter:
start addr L - LSByte of the address of the parameter
N.regs H - MSByte of the number of registers to read (always 0)
N.regs L - LSByte of the number of registers to read
CRC16H - MSByte of CRC16
CRC16L - LSByte of
CRC16
Function 0x06 - Write Single Register
Used to write a single parameter ( 16 bit )
The frame has the following structure:
dev. Addr. func Reg.addr H Reg.addr L Reg. val. H Reg. val. L CRC16H CRC16L
HH 06 HH HH HH HH HH HH
dev. Addr. - Address of the device on the RS485 net (1-247)
Func - Function code = 6
Reg. addr H - MSByte of the address of the parameter
Reg addr L - LSByte of the address of the parameter
Reg. val. H - MSByte of the value of the parameter
Reg val. L - LSByte of the value of the parameter
CRC16H - MSByte of CRC16
CRC16L - LSByte of CRC16
nt with the current state of the device (e.g. day = 31 rejected if month =
4, month = 4 rejected if day = 31).
28