Code Description Cv ∆ P Lbs USD
Z44P ½" press* 3.5 30 psi 2.2 308.00
Z54P ½" press** 3.5 30 psi 2.2 314.00
Z45P ¾" press* 7.5 20 psi 2.2 313.00
Z55P ¾" press** 7.5 20 psi 2.2 319.00
Z45PL ¾" press* 7.5 20 psi 2.3 343.00
Z55PL ¾" press** 7.5 20 psi 2.3 349.00
Z46P 1" press* 7.5 20 psi 2.4 355.00
Z56P 1" press** 7.5 20 psi 2.4 361.00
MOTORIZED ZONE VALVES
Inverted flare sweat adaptors fits Z40, Z50
and inverted flare valve body.
Two-way zone valve. Spring return.
Normally closed actuator.
Auxiliary micro-switch.
Max. body pressure: 300 psi.
Overall length: 5-
5
/
8
"
Temperature range: 32—240°F.
Suitable fluids: water, 50% max. glycol,
15 psi max. steam.
Power supply: 24 V AC.
Power consumption: 5 W, 7 VA.
Rating of auxiliary micro-switch contacts:
0.0 A min, 0.4 A max 24 V (24 V only).
UL873, cULus Listed & CE.
UL 1995 sec. 18 air plenums and ducts.
US Patent 7,048,251.
Two-way zone valve. Spring return.
Normally closed actuator: Z111000.
Auxiliary micro-switch.
Max. body pressure: 300 psi.
Temperature range: 32º—240°F.
Suitable fluids: water, 50% max. glycol,
15 psi max. steam.
Power supply: 24 V AC.
Power consumption: 5 W, 7 VA.
Rating of auxiliary micro-switch contacts:
0.0 A min, 0.4 A max 24 V (24 V only).
18" wire lead connection.
UL873, cULus Listed & CE.
UL 1995 sec. 18 air plenums and ducts.
US Patent 7,048,251.
Z4
2-way
* Two ¾" sweat fittings (NA10006) included.
Two-way zone valve. Spring return.
Normally closed actuator: Z151000
Auxiliary micro-switch.
Max. body pressure: 300 psi.
Temperature range: 32º—240°F.
Suitable fluids: water, 50% max. glycol,
15 psi max. steam.
Power supply: 24 V AC.
Power consumption: 5 W, 7 VA.
Rating of auxiliary micro-switch contacts:
0.0 A min, 0.4 A max 24 V (24 V only).
Screw terminal connection.
UL873, cULus Listed & CE.
UL 1995 sec. 18 air plenums and ducts.
US Patent 7,048,251.
Z5
2-way
* Two ¾" sweat fittings (NA10006) included.
2-way Press
*18" wire lead connection.
**Screw terminal connection.
PL (1) extra long press fitting for retrofit
Includes press fittings.
Code Description Cv ∆ P Lbs USD
Z40 Inverted flare 3.5 30 psi 2.2 229.00
Z40F ¾" Inv flare* 3.5 30 psi 2.2 259.00
Z42 ½" SAE flare 3.5 30 psi 2.2 250.00
Z44 ½" sweat 2.5 50 psi 2.1 223.00
Z45 ¾" sweat 7.5 20 psi 2.2 243.00
Z46 1" sweat 7.5 20 psi 2.3 303.00
Z47 1¼" sweat 7.5 20 psi 2.3 353.00
Code Description Cv ∆ P Lbs USD
Z50 Inverted flare 3.5 30 psi 2.2 235.00
Z50F ¾" Inv flare* 3.5 30 psi 2.2 265.00
Z54 ½" sweat 2.5 50 psi 2.1 229.00
Z55 ¾" sweat 7.5 20 psi 2.2 250.00
Z56 1" sweat 7.5 20 psi 2.3 309.00
Z57 1¼" sweat 7.5 20 psi 2.3 358.00
Code Description Lbs USD
NA10005 ½" sweat 0.3 12.00
NA10006 ¾" sweat 0.3 15.00
NA10007 1" sweat 0.4 24.60
NA61241 Retrofit extension kit 0.2 12.10
Press Installation
Cut tube end square and to desired length. Clean
any debris from inside of tube. Deburr or ream inside
and outside of tube.
Make sure surface is smooth and without burrs or
sharp edges. Insert the tube into the fitting, make
sure the tube is fully inserted and mark with a marker
to indicate proper insertion depth (
7
/
8
”).
Check that the proper clamping jaws are installed
and open jaw arms to set. Place jaw around
valve end and double check proper insertion
depth, press fitting.