Product Overview
Operating principle
When a system contains a primary boiler circuit with its own pump
and a secondary distribution circuit with one or more distribution
pumps, operating conditions may arise in the system where the
pumps interact. This can create abnormal variations in flow rates and
pressures in the circuits.
The HydroLink™ provides a separation chamber on the left side of
the unit to hydraulically separate the boiler circuit from the distribution
circuits: the ow in one circuit does not create a ow in the
other if the pressure loss in the common section is negligible.
This chamber is separated from the manifold chambers by a baffle
plate with two closely spaced openings which, given their size
and placement, act similarly to a pair of closely spaced tees. This
eliminates any significant pressure differential between the upper and
lower manifold chambers that comprise a self-contained manifold
station with up to four independently controlled load circuits delivering
the same supply temperature.
Three possible hydronic balance situations are shown below as
examples.
Gp
G
S1
G
S2
G
S3
G
S4
Gp
G
S1
G
S2
G
S3
G
S4
G
S1
G
S2
G
S3
Gp
G
S4
Gprimary = Gsecondary (G
S1
+G
S2
+G
S3
+G
S4
) Gprimary > Gsecondary (G
S1
+G
S2
+G
S3
+G
S4
) Gprimary < Gsecondary (G
S1
+G
S2
+G
S3
+G
S4
)
primary circuit
secondary circuit
Installation
HydroLink™ units should be installed in accordance with the diagrams
shown in this brochure, ensuring the correct connection of the supply
and return piping and the main (primary) and branch (secondary)
connections. HydroLink™ units can even be installed upside down as
long as the connection logic shown is followed and the air vent and
drain valve are swapped.
The 1/2” NPT female connections must only be used for connecting
an air vent and drain valve (provided with the HydroLink™ assembly)
and not for connecting branch circuits.
Insulation
The Hydrolink™ is supplied with heat-preformed shell insulation. This
provides heat insulation and a sealing affect that prevents atmospheric
water vapor from entering the unit. For this reason, the insulated
HydroLink™ assembly may also be used in cooling water circuits,
as it prevents condensation from forming on the surface of the body.
Support brackets
The HydroLink™ 2+2 and
3+1 models are supplied
complete with suitable
wall-mounting brackets,
making it easy to adjust for
front-to-back positioning.