Product Overview
Insulation
The SEP4
™
comes standard with a preformed insulation shell for 1" to
2" union connections and 2" to 4" flanged connections. Theinsulation is
made of a shell in closed-cell expanded PE-X foam. This insulation ensures
not only perfect heat insulation but also the tightness required to prevent
atmospheric water vapors from entering the unit. Forthese reasons, this
type of insulation can also be used in cooling water circuits, as it prevents
the formation of condensate on the surface of theseparatorbody.
Note: Insulation shells are not available for sizes 5" through 14".
Hydraulic characteristics
The SEP4™ should be sized according to the maximum flow rate of either the primary circuit, or secondary circuit, whichever is largest.
Size 1" 1
1
⁄4" 1
1
⁄2" 2" 2" 2
1
⁄2" 3" 4" 5" 6" 8" 10" 12" 14"
gpm 11 18 26 37 60 80 124 247 300 484 792 1330 1850 2500
m
3
/h 2.5 4.0 6.0 8.5 13.6 18.2 28.2 56 68 110 180 302 420 568
l/s 0.7 1.1 1.6 2.3 3.8 5.0 7.8 15.6 19 30.5 50 84 117 158
Gallons 0.5 0.7 1.3 3.5 4.0 4.0 8.0 8.0 23 23 95 175 255 450
liters 2.0 2.6 5.0 13.2 15.1 15.1 30 30 87 87 360 662 965 1703
Technical specications of insulation, anged versions to 4"
Internal part
Materials: rigid closed cell expanded polyurethane foam
Thickness: 2 3/8" (60 mm)
Density: 2.8 lb/ft
3
(45 kg/m
3
)
Thermal conductivity: 6 BTU
.
in/hr
.
ft
2
.
°F (0.023 W/(m
.
K))
Temperature range: 32–220°F (0–105°C)
Outer part
Materials: embossed aluminum
Thickness: 7.0-mil (0.7 mm)
Reaction to fire (DIN 4102): class 1
Head covers
Heat formed materials: PS
Technical specications of insulation for union connections
Material: closed-cell expanded PE-X
Thickness: 13/16" (20 mm)
Density: - inner part: 1.9 lb/ft
3
(30 kg/m
3
)
- outer part: 5.0 lb/ft
3
(80 kg/m
3
)
Conductivity (ISO 2581): at 32°F (0°C); .16 BTU/in (0.038 W/(m·K)
at 105°F (40°C); .26 BTU/in (0.045 W/(m·K)
Water vapor resistance coefficient (DIN 52615): > 1,300
Temperature range: 32–212°F (0–100°C)
Fire resistance (DIN 4102): class B2