Instructions
Size
1” 1 1/4” 1 1/2” 2” 2” 2 1/2” 3” 4” 5” 6” 8” 10” 12”
gpm 11 18 26 31 40 80 124 247 330 485 792 1320 1850
m
3
/h 2.5 468.5 9 18 28 56 75 110 180 300 420
UNION FLANGED
Installation
The installation of hydronic separator should only be carried out by
qualified personnel in accordance with current legislation.
The hydronic separator is installed between the primary and secondary
circuits, always in a vertical position.
Hydronic
characteristics
The hydronic separator should be sized according to the maximum flow
rate value foreseen at the inlet. The selected value must be either that of
the primary circuit or of the secondary, whichever is the greatest.