Submittal Sheet

Hydro separator
548 series, 2" - 4" with anges
CALEFFI
Application
The hydraulic separator creates a zone with a low pressure loss, which
enables connected primary and secondary circuits to be hydraulically
independent of each other; the flow in one circuit does not create or
interupt flow in another. Hydraulically decoupling primary and secondary
circuits eliminates pump conflict.
Submittal Data 2911 NA — Issue Date 10/2018
Dimensions
Typical Specication
Furnish and install on the plans and described herein, a Caleffi Hydro
Separator
as manufactured by Caleffi. Each separator must be designed
with an epoxy resin painted steel body, 304 stainless steel internal baffle,
preformed insulation, a brass blowdown drain valve and automatic brass air
vent isolated manually with brass shutoff valve. The separator design must
include ANSI B16.5 Class 150 RF flanges. Each separator shall be a Caleffi
model 548 series or approved equal.
(See product instructions for specific installation information.)
Technical data
Materials - separator body: epoxy resin painted steel
- air vent body: brass
- shut off and drain valve body: brass
- internal baffle: 304 stainless steel
Performance
Suitable fluids: water and non-hazardous glycol solution up to 50%
Max. operating pressure: 150 psi (10 bar)
Working temperature range with insulation: 32–220°F (0–105°C)
Working temperature range without insulation (vessel):
32270°F (0–132°C)
Connections - main: 2"-4"ANSI B16.5 150 CLASS RF
- drain valve: 1¼" NPT female
Technical specications of insulation
Internal part
Materials: rigid closed cell expanded polyurethane foam
Thickness: 2 3/8" (60 mm)
Density: 2.8 lb/ft
3
(45 kg/m
3
)
Thermal conductivity: 6 BTU
.
in/hr
.
ft
2
.
°F (0.023 W/(m
.
K))
Temperature range: 32–220°F (0–105°C)
Outer part
Materials: embossed aluminum
Thickness: 7.0-mil (0.7 mm)
Reaction to fire (DIN 4102): class 1
Head covers Heat formed materials: PS
A
1
1
1/4
1
1/2
2
B
8
3/4
9
3/8
10
7/8
12
C
6
1/4
7
3/8
7
3/4
10
1/8
Code
548052A
548062A
548082A
548102A
NA548120A*
NA548150A*
Code
548
006A/96A
548
007A/97A
548
008A/98A
548
009A/99A
Weight (lb)
13
17
25
27
D EC
B
A
A
T
max
120C
P
max
10 bar
T
max
105C
P
max
10 bar
A
8
10
12
Code
NA548200A
NA548250A
NA548300A
B
1¼”
= drain valve size
C D E
A
HYDRO SEPARATOR
Serie 548
T
max
120C
P
max
10 bar
T
max
105C
P
max
10 bar
A
HYDRO SEPARATOR
D
8
5/8
9
1/2
10
1/4
11
7/8
E
8
8
3/8
8
3/4
9
1/2
Flow (gpm)
11
18
26
37
Vol. (gal)
0.5
0.7
1.3
3.5
A
2
2
1/2
3
4
5
6
B
1
1/4
1 1/4
1
1/4
1
1/4
1 1/4
1 1/4
C
13
13
15
15
15
15
D
13
13
18
18
22
22
E
15
15
17
17
19
19
F
14
14
18
18
25
25
Weight (lb)
75
82
112
117
220
231
Flow (gpm)
60
80
124
247
300
484
Vol. (gal)
4.0
4.0
8.0
8.0
22.5
23.2
B
C D E
A A
B
2
2
2
C
39 3/8
43
5/16
47 1/4
D
33 7/8
35
7/8
37 7/8
E
27 1/2
30
31 1/2
F
35 1/2
41
3/4
47 3/4
Weight (lb)
520
725
1,100
Flow (gpm)
792
1,330
1,850
Vol. (gal)
95
175
255
HYDRO-SEPARATOR
Serie 548
T
max
110C P
max
10 bar
38...
2”
= drain valve size
F
F
F
We reserve the right to change our products and their relevant technical data, contained in this publication, at any time and without prior notice. Contractors should request production drawings if prefabricating the system
.
Job name ______________________________________
Job location ______________________________________
Engineer ______________________________________
Mechanical contractor ________________________________
Contractor’s P.O. No. ________________________________
Representative ________________________________
Size ________________________________________
Quantity ________________________________________
Approval ________________________________________
Service ________________________________________
Tag No. ________________________________________
Notes ________________________________________
Calef North America, Inc. 3883 W. Milwaukee Road / Milwaukee, WI 53208
Tel: 414-238-2360 / Fax: 414-238-2366 / www.calef.com
© Copyright 2018 Calef North America, Inc.
Hydraulic characteristics
The hydraulic separator should be sized according to the maximum
flow rate value at the inlet.The selected design value must be the greatest
required flow rate of either the primary circuit or the secondary circuit.
Code A B C D E F
Wt.
(lbs.)
Wt.
(kg)
548052A
2" 13
3
4" 13" 13" 13½" 6
5
8" 75 34
548062A
2½" 13
3
4" 13" 13" 13½" 6
5
8" 82 37
548082A
3" 18
3
8" 15" 17
3
4" 15¼" 8
5
8" 112 51
548102A
4" 18½" 15" 17
3
4" 15½" 8
5
8" 117 53
Flanged connections
Size 2" 2
1
/2" 3" 4"
gpm 60 80 124 247
l/s 3.8 5.0 7.8 16
gallons 4.0 4.0 8.0 8.0
liters 15.1 15.1 30.3 30.3

Summary of content (1 pages)