Submittal Sheet

Technical Data
Threaded and sweat union connections
Materials:
- Body: epoxy resin painted steel
- Drain and shut-off valve: brass
- Air vent body: brass
Suitable fluids: water, or 50% max. glycol solution
Max working pressure: 150 psi (10 bar)
Temperature range:
- with insulation: 32-210°F (0-100°C)
- without insulation: 32-250°F (0-120°C)
Connections:
- Main: 1” & 1 1/4“ sweat & NPT and 1 1/2” & 2” NPT union
- Drain: 3/4“ hose
- Thermometer pocket: 1/2“
Insulation:
- Material: double density closed cell expanded PEX
- Thickness: 3/4” (20 mm)
- Density:
- internal part: 2 lb/ft (30 kg/m3)
- external part: 3 lb/ft (50 kg/m3)
- Thermal conductivity: 32°F (0°C): 9 BTU/in (0.038 W/m·K)
-40°F (-40°C): 11 BTU/in (0.045 W/m·K)
- Coefficient of resistance to the diffusion of vapor: > 1.300
- Temperature range: 32-210°F (0 -100°C)
- Reaction to fire (DIN 4102) : class B 2
Hydraulic characteristics
The hydronic separator should be sized according to the
maximum flow rate at the inlet. The selected design value
must be the greatest between the primary circuit and the
secondary circuit.
Submittal Data 02909 NA - Issue Date 01/2010
548 Series With Union Connections
Hydro Separator
Caleffi North America, Inc. 3883 West Milwaukee Road / Milwaukee, WI 53208
Tel: 414.238.2360 / Fax: 414.238.2366 / www.caleffi.us © Copyright 2010 Caleffi
Size _________________________________
Quantity ______________________________
Approval ______________________________
Service _________________________________
Tag No. _________________________________
Notes _________________________________
Job name ______________________________
Job location ______________________________
Engineer ______________________________
Mechanical contractor ________________________
Contractor’s P.O. No. ________________________
Representative ________________________
We reserve the right to change our products and their relevant technical data, contained in this publication, at any time and without prior notice. Contractors should request production drawings if prefabricating the system.
Typical Specification
Furnish and install on the plans and described herein, a Caleffi Hydro Separator
as manufactured by Caleffi. Each separator must be designed with an epoxy
resin painted steel body, a chrome plated brass blowdown drain valve with hose
connection and automatic brass air vent. The separator design must include
sweat or NPT union fittings. Each separator shall be Caleffi model NA548 or
approved equal. (See product instructions for specific installation information.)
D E C
B
A
A
T
max
120 C
P
max
10 bar
T
max
105 C
P
max
10bar
HYDRO SEPARATOR
Dimensions
CA L E FF I
Note: 96A and 97A have sweat unions, all others have NPT unions.
Size 1" 1 1/4" 1 1/2" 2"
gpm 11.0 18.0 26.0 37.0
l/sec. 0.7 1.1 1.6 2.3
Flow Capacity
Application
The hydronic separator creates a zone with a low pressure loss, which enables
the primary and secondary circuits connected to it to be hydraulically independent
of each other; the flow in one circuit does not create a flow in the other.