Product Overview
Hydro Separator
series 548
CALEFFI
Function
This device consists of several different functional components,
each of which meets specific requirements, typical of the circuits
used in heating and air-conditioning systems.
· Hydronic separator
To keep connected hydronic circuits totally independent from
each other.
· Dirt remover
To permit the separation and collection of any impurities present
in the circuits. Provided with a valved connection with discharge
piping.
· Automatic air vent valve
For automatic venting of any air contained in the circuits.
Provided with a valved connection for maintenance purposes.
Product range
Series 548 NPT F hydronic separator with insulation sizes 1”, 1 1/4”, 1 1/2” and 2” NPT F union
sizes 2”, 2 1/2”, 3“ and 4” ANSI Flangenoitalusni htiw rotarapes cinordyh degnalF 845 seireS
Technical specification
sizes 1” and 1 1/4” sweat unionSeries 548 Sweat hydronic separator with insulation
Series NA548 Flanged hydronic separator without insulation sizes 5”, 6”, 8”, 10” and 12” ASME ANSI Flange
Threaded and sweat union connections
Materials: - Body: epoxy resin painted steel
- Drain and shut-off valve: brass
- Air vent body: brass
Suitable fluids: water, glycol solution
Max percentage of glycol: 50%
Max working pressure: 150 psi (10 bar)
Temperature range: - with insulation: 32÷210°F (0÷100°C)
- without insulation: 32÷250°F (0÷120°C)
Connections: - Main: 1” & 1 1/4“ sweat & NPT and 1 1/2” & 2” NPT union
- Drain: 3/4“ hose
- thermometer pocket: 1/2“
Flanged connections
Materials: - Body: epoxy resin painted steel
- Drain and shut-off valve brass
- Air vent body brass
Suitable fluids: water, glycol solution
Max percentage of glycol: 50%
Max working pressure: 150 psi (10 bar)
Temperature range: - with insulation: 32÷220°F (0÷105°C)
- without insulation: 32÷250°F (0÷120°C)
Connections: - Flanged: 2” ÷ 12” ANSI 150 CLASS
- Drain: 1 1/4” & 2” NPT F
- Material: double density closed cell expanded PEX
- Thickness: 3/4” (20 mm)
- Density: - internal part: 2 lb/ft (30 kg/m
3
)
- external part: 3 lb/ft (50 kg/m
3
)
- Thermal conductivity: 32ºF (0°C): 9 BTU/in (0.038 W/m·K)
-40ºF (-40°C): 11 BTU/in (0.045 W/m·K)
- Coefficient of resistance to the diffusion of vapor: > 1.300
- Temperature range: 32-210ºF (0 -100ºC)
- Reaction to fire (DIN 4102) : class B 2
Technical specifcation of insulation for fanged versions up to 4”
Internal part
- Material: rigid closed cell expanded polyurethane foam
- Thickness: 2 3/8” (60 mm)
- Density: 3 lb/ft (45 kg/m
3
)
- Thermal conductivity: 6 BTU/in (0.023 W/m·K)
- Temperature range: 32-220 º F (0 – 105°C)
External cover
- Material: embossed aluminium
- Thickness: 7.0-mil (0.7 mm)
- Reaction to fire: class 1
Head covers
- Heat moulded material: PS
Technical specifcation of insulation for union connection versions
*NA prefix indicates ASME tagged and registered with the National Board of Boiler and Pressure Vessel Inspectors
01076/08 NA
Replaces 01076/06 NA
R
E
G
I
S
T
E
R
E
D
BSI EN ISO 9001:2000
Cert. n° FM 21654
UNI EN ISO 9001:2000
Cert. n° 0003