Installation
1. Filling valve can be installed in either horizontal or vertical position.
Donot install upside down. Do not install outdoors.
2. Caleffi recommends the AutoFill
5350 series filling valve be installed
with separately-purchased shut-off ball valves, code NA39589,
upstream and downstream.
3. The AutoFill
5350 series filling valve does not have an internal
check valve to prevent reverse flow of water. For this reason,
a backflow preventer installed upstream is recommended. Use
a Caleffi code 573503A, or other brand that complies with
applicable codes.
4. The system pressure is factory pre-set to 15 psi (1.035 bar).
a. To properly reset to a higher desired system pressure (greater than 15
psi), start by opening the inlet shut-off valve while keeping the outlet
shut-off valve closed. Adjust the operating knob clockwise (+) to
increase the system pressure to the desired value as indicated on the
outlet gauge, approximately 7 psi per revolution.
b. To reset to a lower system (lower than 15psi), turn the operating
knob counterclockwise (-) until it stops turning, 0psi. Then, open
the inlet shut-off valve while keeping the outlet shut-off valve
closed. Adjust the operating knob clockwise (+) to increase the
system pressure to the desired value as indicated on the outlet
gauge, approximately 7 psi per revolution.
5. When the desired system pressure is indicated on the gauge, open
the outlet shut-off valve, filling the system.
6. The system will begin filling in fast-fill mode, then automatically stop
filling when system pressure reaches the setting value. Thereafter,
the internal mechanism will automatically control system pressure to
the desired value.
Maintenance
When checking, cleaning or replacing the complete regulating cartridge:
1. Isolate the filling valve.
2. The special construction of the filling unit does not require any
adjustment of the system pressure, which can be left at the set value.
3. Remove the upper cover. The upper cover is integral with the internal
regulating cartridge.
4. Check and clean the filter.
5. When the cartridge is screwed back into the body, the pressure
setting will return to the original value.
6. Reopen the shut-off valves. The pressure will return to the original
setvalue.