Brochure
71
6
B
Check valve fits 116 ThermoSetter
TM
.
DZR low-lead brass.
Max. working pressure: 150 psi.
Max. working temperature: 250°F.
Code Description Lbs USD
NA10469 ½" FNPT x MNPT inline check valve 0.1 35.60
NA10467 ¾" FNPT x MNPT inline check valve 0.1 41.50
Thermo-electric actuator with micro-switch
fits on 676 two-way zone valve bodies.
Low current draw.
Protection class (installed in all positions):
NEMA 3 (IP54).
Power supply: 24 V AC/DC.
Initial current draw: ≤250 mA.
Power consumption:
holding: 3 W
inrush: 6 VA
Rating of micro-switch contacts: 5 A (24 V).
31.5" wire lead connection.
6564
Code Description Lbs USD
656404 24 V AC/DC 0.4 65.00
656414 24 V AC/DC with micro-switch 0.4 82.10
Temperature gauge fits 116 series.
Working temperature range: 30°F — 180°F.
Code Description Lbs USD
116010 1½" dial temp. gauge 0.1 11.80
Insulation shell fits 116 series thermal
balancing valve.
Code Description Lbs USD
CBN116140 Insulation shell for 1161, 1162, 1163 0.1 28.40
CBN116440 Insulation shell for 1164 0.1 28.00
Replacement thermal disinfection cartridge.
Code Description Lbs USD
F0000580 Replacement thermal bypass cartridge 0.1 41.50
Actuator disinfection cartridge for use with
656 actuator.
Code Description Lbs USD
116000 Replacement actuator bypass cartridge 0.1 53.40
THERMAL BALANCING VALVES FOR PLUMBING
TwisTop™ thermo-electric actuator for use
with 1163xx Series.
Twist the top to manually open.
Power supply: 24 V AC/DC.
Initial current draw: ≤ 250 mA.
Power consumption: 3 W.
Rating of micro-switch contacts: 5 A (24 V).
31.5" wire lead connection.
US Patent 7,617,989 B2.
6563
TwisTop
™
Code Description Lbs USD
656344 24 V AC/DC 0.4 87.10
656354 24 V AC/DC with micro-switch 0.4 103.00
Adjustable thermal balancing valve for
domestic hot water recirculation circuits.
Drywell for temperature gauge or probe.
DZR low-lead brass body.
Optional outlet check valve.
Max. working pressure: 230 psi.
Adjustment temperature range: 105°F —150°F.
Cv max: 2.1; Cv min: 0.35.
Cv design: 0.69.
Certified to Low Lead Laws and listed by
ICC-ES for use in accordance with the U.S.
and Canadian plumbing codes.
ANSI/NSF 61 to 180°F approval.
116
ThermoSetter
™
Code Description Lbs USD
116440A ½" FNPT 1.6 160.00
116440AC ½" FNPT, check valve 1.8 194.00
116441A ½" FNPT, gauge 1.5 170.00
116441AC ½" FNPT, gauge, check valve 1.7 206.00
116450A ¾" FNPT 1.6 172.00
116450AC ¾" FNPT, check valve 1.8 212.00
116451A ¾" FNPT, gauge 1.5 182.00
116451AC ¾" FNPT, gauge, check valve 1.7 224.00
NEW
NEW
NEW
NEW
Function
The ThermoSetter™ adjustable thermal balancing valve is used
for automatic balancing of recirculation loops in domestic hot
water systems, to speed hot water delivery, reduce water waste
and save energy. The internal thermostatic balancing cartridge
automatically modulates flow to ensure a constant temperature in
the recirculation piping system. The 116 Series has an adjustment
knob with temperature scale indication. An integral dry-well holds a
slide-in temperature gauge for local indication, or a sensor for remote
temperature sensing. The optional check valve protects against circuit
thermo-syphoning.