Product Overview
01239/13 NA
HydroMixer
™
motorized temperature
mixing unit
167 series
Function
The 167 series HydroMixer™ provides a modulating three-point
floating type non-spring return motorized three-way mixing valve
to regulate the fluid temperature in heating and air conditioning
systems in response to a separately-sourced outdoor reset controller.
It comes complete with onboard three-speed or variable-speed
pump, motorized three-way mixing valve, check valve, supply and
return temperature gauges, secondary circuit shut-off ball valves
and pre-formed insulation shell. Versions are available with either the
three-speed Grundfos UPS 15-58 pump or the variable-speed Alpha
25-55U pump.
The unit can be ordered with supply flow and pump on the right or left
side. The adjustable differential pressure by-pass valve, code 519600
and wall bracket code 165001 are optional. The unit comes with male
union connections which require separately purchased, 1 inch sweat
or NPT, top outlet and bottom inlet fitting kits.
Product Range
Code 167600A Motorized temperature mixing valve with Grundfos UPS 15-58 pump on right side..............connections 1” sweat or NPT union*
Code 167610A Motorized temperature mixing valve with Grundfos UPS 15-58 pump on left side...............connections 1” sweat or NPT union*
Code 167602A Motorized temperature mixing valve with Grundfos Alpha 25-55U pump on right side..........connections 1” sweat or NPT union*
Code 167612A Motorized temperature mixing valve with Grundfos Alpha 25-55U on left side......................connections 1” sweat or NPT union*
*Fitting sets sold separately
CALEFFI
Technical characteristics
Materials
Motorized three-way valve
Body: brass
Valve plug: brass
Seals: EPDM
Connecting pipes
Material: steel
Check valve
Body: brass
Shutter: PPAG40
Shut-off ball valves
Body: brass
Actuator (three point floating type non-spring return)
Synchronous motor
Supply voltage: 24 VAC
Power consumption: 6 VA
Micro-switch contact rating: 6 (2) A (24 V)
Time to rotate 90° both directions: 50 s
Max. ambient temperature: 14 – 130°F (-10°C – 55°C)
Wire lead length: 31 in. (79 cm)
Performance
Suitable fluids: water, glycol solution
Max. percentage of glycol: 30%
Max. working pressure: 145 psi (10 bar)
Primary inlet temperature range: 40–212°F (5–100°C)
Connections: male union
threads
- top outlets: 1-1/4” male straight
- bottom inlets: 1-1/2” male straight
- inlet/outlet center distance: 5 inches (125 mm)
Pump
Three-speed pump: Grundfos: UPS 15-58-130;
Variable-speed pump: Grundfos: ALPHA 25-55U;
Body material: cast iron
Power supply: 115V 50/60 Hz
Protection class: Class F
Pump center distance: 5-1/8” (130 mm)
Pump connections: 1 1/2” male straight
Temperature gauges
Dual scale: 32 –176°F (0 – 80°C)
Technical specification of insulation
Material: EPP
Thickness: 1 1/8” (30 mm)
Density: 3 lb/ft
3
(45 kg/m
3)
Working temperature range: 25–250°F (-5–120°C)
Thermal conductivity: 0.037 W/(m·K) at 10°C
Fire resistance (UL94): class HBF
Adjustable Differential by-pass valve code 519006 (optional)
Body: brass
Valve plug: EPDM
Spring: stainless steel
Seals: EPDM
Max. working pressure: 145 psi (10 bar)
Max. working temperature: 212°F (100°C)
By-pass differential pressure setting range: 0.3 – 4.3 psi (2 – 30 kPa)
Connections: 1” male x 1” male (straight)
Wall bracket code 165001 (optional)
Material: stainless steel
ACCREDITED
ISO 9001 No. 0003
ISO 9001 FM 21654