User Guide
CAUTION: If the balancing valve valve is not installed, commissioned and
maintained properly, according to the instructions contained in this
manual, it may not operate correctly and may endanger the user.
CAUTION: Make sure that all the connecting pipework is water tight.
Caleffi North America, Inc.
3883 West Milwaukee Road
Milwaukee, WI 53208
T: 414.238.2360 F: 414.238.2366
1.
Remove the protective strip from the adhesive
surface. Re-close the
insulation shells.
2.
If the balancing valve with flow meter is used with chilled water, spread a
thin layer of sealant on the edge of the insulation and wait until the solvent
evaporates (10 minutes approx.) and then re-close it.
Procedure for
installation and
insulation
assembly
1.
Remove bypass valve assembly with an 8 mm wrench.
2.
Install replacement bypass valve assembly, code F19346, using locktight
to seal the threads.
Procedure for
replacing bypass
valve stem with
operating ring
7-19-18