Function
The balancing valve ac c urately controls the flow rate of heating and
cooling transfe r fluid supplied to fan coils and termina l units; or where
flow balancing is required in solar thermal systems. Proper hydronic
syste m balancing ensures the s ystem operates acc ording to design
specifications, providing satisfactory thermal comfort with low energy
consumption.
The flow meter is housed in a by-pas s circuit on the valve body and
can be shut off during normal operation. The flow meter p ermits
fast and easy circuit balancing without added differential pressure
gages and c harts. Th balancing valve comes standard with a hot
pre-formed insulation shell to optimize thermal performance for both
hot and c hilled water.
Product range
132 S eries B alanc ing valve with flow meter s izes 1/2”, 3/4,
1”, 1 1/4, 1 1/2 and 2"
Technical characteristics
Va lve
Material: B od y and ball: bras s
B all c ontrol s tem: chrome plated bras s
B all s eal seat: PTFE
C ontrol s tem gu ide: PS U
S eals: E PDM
F low m eter
Material: B od y: bras s
Headwork: bras s EN 12164 C W614N
Valve stem: chrome plated bras s
S prings: stainless s teel
S eals: E PDM
Flow meter float and indicator cover: PS U
Performance: Medium: water, gly c ol solutions
Max. percentage of glyc ol: 50%
Max. working pres sure: 150 psi (10 bar)
Working temperature range: 1 4 - 230°F (-10–11C )
Flow rate range unit of meas u rement: gpm
Acc uracy: ±10%
C ontrol s tem angle of rotation: 90°
R equired operating wrench: 1/2–1 1/4”: 9 mm
1 1/2 and 2: 12 mm
Threaded c onnections: 1/2 2 FNPT
Flow rate c orrection factor: 20% -30% gly c ol solutions: 0.9
40%-50% glycol solutions: 0.8
Ins ula tion
Material: closed c ell expanded PE-X
Thickness: 10 mm
Density: - inner part: 30 kg/m
3
- outer part: 50 kg/m
3
Thermal c onduc tivity (DIN 52612): - at 0°C : 0.038 W/(K )
- at 4C : 0.045 W/(K )
C oefficient of res is tance to water vapor (DIN 52615): > 1.30 0
Wo rking temperature range: 32 - 212 F (0–10C )
R eac tion to fire (DIN 4102): clas s B 2
CALEFFI
QuickSetter™ Balancing Valve with flow meter
132 Series
18106.04
www.caleffi.com
© Copyright 2018 Caleffi
These items are designed for use in
closed hydronic systems. Do not
use in plumbing applications. These
items do not meet the low-lead
plumbing standards of U.S. and
Canada.