Submittal Form

CALE FFI
QuickSetter™ Balancing Valve With Flow Meter
132 Series
Submittal Data 02934 NA — Issue Date 10/2011
Dimensions
A B
C
A
D
CALEFFI
7
6
5
4
3
2
230°F
3/4” NPT
GPM
150 psi
We reserve the right to change our products and their relevant technical data, contained in this publication, at any time and without prior notice. Contractors should request production drawings if prefabricating the system.
Job name ______________________________________
Job location ______________________________________
Engineer ______________________________________
Mechanical contractor ________________________________
Contractor’s P.O. No. ________________________________
Representative ________________________________
Size ________________________________________
Quantity ________________________________________
Approval ________________________________________
Service ________________________________________
Tag No. ________________________________________
Notes ________________________________________
Caleffi North America, Inc. 3883 West Milwaukee Road / Milwaukee, WI 53208
Tel: 414.238.2360 / Fax: 414.238.2366 / www.caleffi .us
© Copyright 2011 Caleffi
1
0.1
1
0.2
0.3
0.5
200
500
Δp (psi)
G
(l/h) (
gpm
)
10
2
3
5
20
1
2
3
5
4
0.4
0.1
0.2
0.3
0.5
(psi) (bar)
10
20
0.4
4
1000
2000
0.1
0.03
0.05
0.04
.010
.020
.01
.20
.30
.50
.40
5000
10000
20000
1
0. 2
0. 5
2
5
10
2
0
5
0
10 0
2
00
50
1/2”
3/4”
1”
1 1/4”
1 1/2”
00
2”
(feet)
46.20
23.10
11.55
9.24
6.93
4.62
2.31
1.16
0.924
0.693
0.462
0.231
Code A B- in B- mm C- in C- mm D- in D- mm
Weight
(lb)
Weight
(kg)
132432A
132552A
132662A
132772A
132882A
132992A
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
3-5/16
3-5/16
3-3/8
3-1/2
3-5/8
3-3/4
83.5
83.5
85
88
91
95
1-13/16
1-13/16
1-7/8"
2"
2-1/4"
2-1/2"
45.5
45.5
47
50
56.5
63
5-3/4"
5-3/4"
6-1/4"
6-1/2"
6-3/4"
7"
145
145
158
163.5
171
178
2.0
1.8
2.4
2.8
3.4
4.4
0.9
0.81
1.08
1.3
1.5
2.0
Hydraulic characteristics at 100% open
Typical Speci cation
Furnish and install on the plans and describing herein, a Caleffi balancing valve with fl ow meter,
as manufactured by Calef . Each balancing valve must be designed with a brass body, ball
control stem, fl ow meter body, headwork, and shutoff control stem, chrome-plated; EPDM
seals and pre-formed shell insulation in expanded closed cell PE-X. The balancing valve
must include NPT female threaded connections for 3/4”, 1”, 1-1/4”, 1-1/2”, 2” sizes. Each
valve has 150 psi (10 bar) maximum working pressure and 14 - 230°F (-10 – 110°C) working
temperature range, and ± 10% measurement accuracy. Each valve shall be Caleffi model 132
or approved equal. (See product instructions for specifi c installation information.)
Technical Data
Valve materials:
- Body and ball: brass
- Ball control stem: chrome plated brass
- Ball seal seat: PTFE
- Control stem guide: PSU
- Seals: EPDM
Flow meter materials:
- Body: brass
- Headwork: brass EN 12164 CW614N
- Bypass valve stem: brass, chrome plated
- Springs: stainless steel
- Flow meter fl oat and indicator cover: PSU
Performance: Suitable fl uids: water, gylcol solutions
- Max. percentage of glycol: 50%
- Max. working pressure: 150 psi (10 bar)
- Working temperature range: 14–230°F (10 –110°C)
- Flow rate range unit of measurement: gpm
- Accuracy: ±10%
- Control stem angle of rotation: 90°
- Required operating wrench: 1/2” - 1-1/4” (9 mm)
1-1/2” - 2” (12 mm)
Threaded connections: 1/2” - 2” FNPT
Insulation material: closed cell expanded PE-X
- Thickness: 25/64” (10 mm)
- Density, inner part: 1.9 lb/ft
3
(30 kg/m
3
)
- Density, outer part: 3.1 lb/ft
3
(50 kg/m
3
)
- Thermal conductivity (DIN 52612):
-at 32°F (0° C): 0.263 BTU·in/hr·ft
2
·0°F (0.038 W/ (m-K)
-at 104°F (40° C): 0.312 BTU·in/hr·ft
2
·0°F (0.045 W/ (m-K)
- Coeffi cient of resistance to water vapor (DIN 52615): >1,300
- Working temperature range: 32 - 212°F (0 -100°C)
- Reaction to fi re (DIN 4102): class B2
Application
The 132 series balancing valve accurately sets the fl ow rate of heating and cooling transfer
uid supplied to fan coils and terminal units or where fl ow balancing is required in solar thermal
systems. Proper hydronic system balancing ensures that the system operates according to
design specifi cations, providing satisfactory thermal comfort with low energy consumption. The
ow meter is housed in a bypass circuit on the valve body and can be shut off during normal
operation. The fl ow meter permits fast and easy circuit balancing without added differential
pressure gauges and reference charts. The balancing valve is furnished with a preformed
insulation shell to optimize thermal performance for both hot and cold water systems.
Cod e Connection Flow rate (GPM ) C v
132 432A 1/2” NPT 1/2 – 1 3/4 1.0
132 552A 3/4” NPT 2.0 – 7.0 6.3
132 662A 1” NPT 3.0 – 10.0 8.3
132 772A 1 1/4” NPT 5.0 – 19.0 15.2
132 882A 1 1/2” NPT 8.0 – 32,0 32.3
132 992A 2” NPT 12.0 – 50,0 53.7
NOTE: Flow rate correction factor: 20%-30% glycol solutions: 0.9
40%-50% glycol solutions: 0.8

Summary of content (1 pages)