132 series Balancing valve with flow meter, threaded connections ½”, ¾”, 1”, 1 ¼”, 1 ½”, and 2" NPT female
132 series Balancing valve with flow meter, flanged connections 2 ½”, 3”, 4” ANSI 125
CALEFFI
Function
The 132 series balancing valve accurately sets the flow rate of
heating and cooling transfer fluid supplied to fan coils and terminal
units or where flow balancing is required in solar thermal systems.
Proper hydronic system balancing ensures that the system operates
according to design specifications, providing satisfactory thermal
comfort with low energy consumption. The flow meter is housed in a
bypass circuit on the valve body and can be shut off during normal
operation. The flow meter permits fast and easy circuit balancing
without added differential pressure gauges and reference charts. The
threaded version is furnished with a hot pre-formed insulation shell to
optimize thermal performance for both hot and cold water systems.
Patent pending.
ISO 9001 No. 0003
ACCREDITED
ISO 9001 FM 21654
Series 132 threaded 132 anged
Materials
Valve
Body:
Ball:
Ball control stem:
Ball seal seat:
Control stem guide:
Seals:
Flow meter
Body:
Bypass valve stem:
Springs:
Seals:
Flow meter float and indicator cover:
brass
brass
brass, chrome-plated
PTFE
PSU
peroxide-cured EPDM
brass
brass, chrome-plated
stainless steel
peroxide-cured EPDM
PSU
cast iron
brass
brass, chrome-plated
R-PTFE
PTFE
peroxide-cured EPDM
brass
brass, chrome-plated
stainless steel
peroxide-cured EPDM
PSU
Performance
Suitable Fluids:
Max. percentage of glycol:
Max. working pressure:
Working temperature range:
Flow rate range unit of measurement:
Accuracy:
Control stem angle of rotation:
Control stem adjustment wrench:
Connections:
Flow rate correction factor:
water, glycol solutions
50%
150 psi (10 bar)
14 - 230º F (-10 - 110º C)
gpm
±10%
90º
½" - 1¼": 9 mm
1½" - 2": 12 mm
½" - 2": NPT female
20% - 30% glycol solutions: 0.9
40% - 50% glycol solutions: 0.8
water, glycol solutions
50%
150 psi (10 bar)
14 - 230º F (-10 - 110º C)
gpm
±10%
90º
with 5½" diameter handwheel
2½", 3" and 4": ANSl B16.1
125 CLASS RF flanged
20% - 30% glycol solutions: 0.9
40% - 50% glycol solutions: 0.8
Insulation
Material:
Thickness:
Density:
Thermal conductivity (DIN 52612):
Coefficient of resistance to water vapor (DIN 52615):
Working temperature range:
Reaction to fire (DIN 4102):
closed cell expanded PE-X
25/64 inch (10 mm)
- inner part: 1.9 lb/ft
3
(30 kg/m
3
)
- outer part: 3.1 lb/ft
3
(50 kg/m
3
)
- at 32°F (0°C):
0.263 BTU·in/hr·ft2·°F (0.038 W/(m·K))
- at 104°F (40°C):
0.312 BTU·in/hr·ft2·°F (0.045 W/(m·K))
< 1,300
32 - 212º F (0 - 100º C)
class B2