Technical specications
Materials
Valve
Body: DZR low-lead brass
Ball: stainless steel
Ball control stem: brass, chrome plated
Ball seal seat: PTFE
Control stem guide: PSU
Seals: EPDM
Flow meter
Body and headwork: DZR low-lead brass
Bypass valve stem: stainless steel
Springs: stainless steel
Seals: EPDM
Flow meter float and indicator cover: PSU
NSF/ANSI 372-2011, Drinking Water System Components-Lead Content
Reduction of Lead in Drinking Water Act, California Health and Safety Code
116875 S.3874, Reduction in Drinking Water Act, certified by ICC-ES, file PMG-1360.
Performance
Suitable Fluids: water, glycol solutions
Max. percentage of glycol: 50%
Max. working pressure: 150 psi (10 bar)
Working temperature range: 14 - 230°F (-10–110°C)
Flow rate range unit of measurement: 1/2 - 1 ¾ gpm
2 - 7 gpm
Accuracy: ±10%
Control stem angle of rotation: 90°
Control stem adjustment wrench: 9 mm
Connections
Main connections:
½”, ¾”, 1”
sweat union
¾”
press union
Lay length (press connection): size
¾
inch without gauge: 7
5
/16"
size
¾
inch with gauge: 10
1
/8"
Function
The QuickSetter+™ manual balancing valve contains a built-in flow
meter and sight gauge, negating the need for differential pressure
gauges and reference charts. Circuit balancing is fast, easy and
accurate. Constructed of DZR low-lead brass, QuickSetter+™ is
ideally suited for use in plumbing applications such as hot water
recirculation systems. The built-in check valve protects against circuit
thermo-siphoning. The outlet temperature gauge (optional) verifies the
fluid temperature in the circuit. The flow meter sight gauge is dry (not
exposed to the fluid) thus eliminating the possibility of gauge clouding/
scaling over time. The QuickSetter+™ can also be used in heating
systems.
Flow rate ranges
Code Connection Flow rate (gpm)
Fully
open
Cv
132439AFC
½" sweat 0.5 - 1.75 1.0
132536AFC
¾" press 0.5 - 1.75 1.0
132539AFC
¾" sweat 0.5 - 1.75 1.0
132639AFC
1" sweat 0.5 - 1.75 1.0
132459AFC
½" sweat 2.0 - 7.0 6.3
132556AFC
¾" press 2.0 - 7.0 6.3
132559AFC
¾" sweat 2.0 - 7.0 6.3
132659AFC
1" sweat 2.0 - 7.0 6.3
Code Connection Flow rate (gpm)
Fully
open
Cv
132438AFC*
½" sweat 0.5 - 1.75 1.0
132537AFC*
¾" press 0.5 - 1.75 1.0
132538AFC*
¾" sweat 0.5 - 1.75 1.0
132638AFC*
1" sweat 0.5 - 1.75 1.0
132458AFC*
½" sweat 2.0 - 7.0 6.3
132557AFC*
¾" press 2.0 - 7.0 6.3
132558AFC*
¾" sweat 2.0 - 7.0 6.3
132658AFC*
1" sweat 2.0 - 7.0 6.3
*with temperature gauge.
ISO 9001 No. 0003
ACCREDITED
ISO 9001 FM 21654
Product range
132 series Balancing valve with flow meter, includes check valve
and optional outlet temperature gauge.............................................................connections
½”, ¾”, 1”
sweat union and
¾”
press union
Replaces 01283/14 NA