Submittal Sheet
Code A B C D
Wt
(lb)
132438AFC* 1/2" 3 5/16" 1 13/16" 9 11/16" 2.50
132538AFC* 3/4" 3 5/16" 1 13/16" 9 13/16" 2.60
132638AFC* 1" 3 5/16" 1 13/16" 10 1/8" 2.70
132458AFC* 1/2" 3 5/16" 1 13/16" 9 11/16" 2.50
132558AFC* 3/4" 3 5/16" 1 13/16" 9 13/16" 2.60
132658AFC* 1" 3 5/16" 1 13/16" 10 1/8" 2.70
QuickSetter
+
™ Low-lead
balancing valve with flow meter
132 series
CALEFFI
Technical Data
Materials
Valve
Body: DZR low-lead brass
Ball: stainless steel
Ball control stem: brass, chrome plated
Ball seal seat: PTFE
Control stem guide: PSU
Seals: EPDM
Flow meter
Body and headwork: DZR low-lead brass
Bypass valve stem: stainless steel
Springs: stainless steel
Seals: EPDM
Flow meter float and indicator cover: PSU
Reduction of Lead in Drinking Water Act Compliant: 0.25% Max.
weighted average lead content. Reduction of Lead in Drinking Water
Act Certifed by IAPMO R&T.
Performance
Suitable Fluids: water, glycol solutions
Max. percentage of glycol: 50%
Max. working pressure: 150 psi (10 bar)
Working temperature range: 14 - 230°F (-10–110°C)
Flow rate range unit of measurement: 1/2 - 1 3/4 gpm; 2 - 7 gpm
Accuracy: ±10%
Control stem angle of rotation: 90°
Control stem adjustment wrench: 9 mm
Sweat connections: 1/2”, 3/4", 1"
Application
The QuickSetter+™ manual balancing valve contains a built-in flow
meter and sight gauge, negating the need for differential pressure
gauges and reference charts. Circuit balancing is fast, easy and
accurate. Constructed of low-lead brass, QuickSetter+™ is ideally
suited for use in plumbing applications such as hot water recirculation
systems. The built-in check valve protects against circuit thermo-
siphoning. The outlet temperature gauge (optional) verifies the fluid
temperature in the circuit. The flow meter sight gauge is dry (not
exposed to the fluid) thus eliminating the possibility of gauge clouding/
scaling over time.
Submittal Data 02936 NA — Issue Date 10/2014
Dimensions
D
C
B
MIX
D
30
50
70
90
110
130
150
170
190
210
˚F
A
0.50
0.50
1.00
0.75
0.75
1.00
1.25
1.25
1.50
1.75
P.
MAX 150 psi
T.
MAX 230˚F
GPM
1.50
1.75
Code A B C D
Wt
(lb)
132439AFC 1/2" 3 5/16" 1 13/16" 8 3/8" 2.00
132539AFC 3/4" 3 5/16" 1 13/16" 8 7/16" 2.10
132639AFC 1" 3 5/16" 1 13/16" 8 9/16" 2.25
132459AFC 1/2" 3 5/16" 1 13/16" 8 3/8" 2.00
132559AFC 3/4" 3 5/16" 1 13/16" 8 7/16" 2.10
132659AFC 1" 3 5/16" 1 13/16" 8 9/16" 2.25
*with temperature gauge.
Typical Specification
Furnish and install on the plans and described herein, a Caleffi QuickSetter+™
balancing valve with flow meter as manufactured by Caleffi. Each balancing
valve must be designed with DZR low-lead brass body (<0.25% Lead
content) certified by IAPMO R&T, stainless steel ball, chrome-plated brass
ball control stem, PTFE ball seal seat, PSU control stem guide, DZR low-
lead brass flow meter body and headwork, stainless steel flow meter bypass
valve stem, stainless steel flow meter springs, PSU flow meter float and
indicator cover, EPDM seals, and provided complete with inlet flow check
valve. Can be provided with optional mixed outlet termperature gauge, 30 to
210°F scale, 2 inch diameter. Each balancing valve shall be a Caleffi model
132 or approved equal. (See product instructions for specific installation
information.)
We reserve the right to change our products and their relevant technical data, contained in this publication, at any time and without prior notice. Contractors should request production drawings if prefabricating the system.
Job name ______________________________________
Job location ______________________________________
Engineer ______________________________________
Mechanical contractor ________________________________
Contractor’s P.O. No. ________________________________
Representative ________________________________
Size ________________________________________
Quantity ________________________________________
Approval ________________________________________
Service ________________________________________
Tag No. ________________________________________
Notes ________________________________________