Product Overview
PRODUCT RANGE - FLOWCAL
™
127 SERIES
03580-14NA
Calef North America, Inc. · 3883 W. Milwaukee Road · Milwaukee, WI 53208
Tel. 414-238-2360 · Fax 414-238-2366
sales@calef.com · www.calef.us
© Copyright 2014 Calef North America, Inc.
WE RESERVE THE RIGHT TO CHANGE OUR PRODUCTS AND THEIR RELEVANT
TECHNICAL DATA, CONTAINED IN THIS PUBLICATION, AT ANY TIME AND WITHOUT
PRIOR NOTICE.
REFERENCE DOCUMENTATION: TECHNICAL BROCHURE 01166
TECHNICAL SPECIFICATIONS
130 SERIES
CODE CONNECTIONS
127341AF... 1/2” NPT Male
127349AFA... 1/2” Sweat
127351AF... 3/4” NPT Male
127359AF... 3/4” Sweat
127356AF... 3/4” Press
127361AF... 1” NPT Male
127369AF... 1” Sweat
Max. working pressure: 232 psi.
Working temperature range: 32 to 212°F.
DZR Low-Lead Brass (less than 0.25% lead content certified by IAPMO R&T).
The FLOWCAL flow cartridge is composed
of a cylinder, a spring-loaded piston, and a
combination of fixed and variable geometric
orifices through which the fluid flows. These
variable orifice sizes increase or decrease
by the piston movement, contingent on the
system’s fluid thrust. A specially calibrated
spring counteracts this movement to
regulate the amount of fluid which may pass
through the valve orifices, maintaining a
balanced system. FLOWCAL valves are high
performance automatic flow balancing valves
which control selected flow rates within a tight
tolerance (approximately 10%) and offer a
wide range of operation.
GPM
LAST 3
DIGITS*
...
∆P CONTROL
RANGE (PSID)
1/2 G50
2 - 14
3/4 G75
1 1G0
2 - 32
1.5 1G5
2 2G0
2.5 2G5
3 3G0
3.5 3G5
GPM
LAST 3
DIGITS*
...
∆P CONTROL
RANGE (PSID)
4 4G0
2 - 324.5 4G5
5 5G0
6 6G0
4 - 347 7G0
8 8G0
9 9G0
5 - 35
10 10G
To balance hydronic fan coil circuits.
APPLICATION DIAGRAMS
OPERATION WITHIN THE ∆P CONTROL RANGE
FLOW RATE
Nominal
Control range
Initial
Final
2 psi 32 psi
ΔP
∆P
∆P
If the differential pressure is within the control range, the spring-loaded
piston is positioned to give the fluid a free flow area permitting constant
flow at the nominal rate for which the FLOWCAL is set up.
To balance domestic hot water recirculation circuits.
*Last three digits of code number.