User Guide

Series 1164
Thermal balancing valve for domestic hot water recirculation circuits. Dezincification resistant low-lead brass body (<0.25% Lead
content), complies with NSF/ANSI 372, low lead, as certified by ICC-ES, file PMG-1360.. Complies with codes IPC, IRC, UPC
and NPC and standard NSF/ANSI/CAN 61, as certified by ICC-ES, file PMG-1512 (180°F/82°C Commercial Hot). Sizes ½" and
¾" with NPT female connections. Adjustable thermostatic cartridge. Peroxide-cured EPDM hydraulic seals. Temperature gauge/
probe dry-well Ø 10 mm. Maximum working pressure 230 psi (16 bar). Maximum differential pressure 15 psi (1 bar). Adjustment
temperature range 105–150°F (40 – 65°C). Flow rating: 2.1 Cv (1.8 Kv) maximum, 0.35 Cv (0.3 Kv) minimum, 0.69 Cv (0.6 Kv)
design. Equipped with: ABS adjustment knob with temperature adjustment scale for manual setting and tamper-proof adjustment
locking screw. Provide with optional outlet temperature gauge with 30°F to 180°F (0°C-80°C) temperature scale. Provide with
optional check valve. Pre-formed insulation shell is available for field installation.
SPECIFICATION SUMMARY
We reserve the right to make changes and improvements to the products and related data in this publication, at any time and without prior notice.
Caleffi North America, Inc.
3883 W. Milwaukee Road
Milwaukee, WI 53208
Tel: 414-238-2360 · Fax: 414-238-2366
sales@caleffi.com · www.caleffi.com
© Copyright 2020 Caleffi North America, Inc.
Maintenance
The adjustable balancing cartridge can be removed from the valve body
for periodic inspection, cleaning or replacement.
Accessories
ThermoSetter codes 116440A(C) and 116450A(C) come standard
without temperature gauge, but temperature gauge, code 116010 can
be field-installed later for confirming the temperature of the hot water in
the circuit.
The temperature gauge dry-well can also be used for inserting a special
immersion probe (with Ø < 10 mm) for remote control of the disinfection
temperature by a dedicated electronic control unit.
Insulation shell
The ThermoSetter thermal balancing valve can be supplied with an
optional insulation shell, code CBN116440 purchased separately, to
minimize heat loss.