Brochure
73
6
B
Fast-coupling pressure test ports The 130 series balancing valve has as
standard probe type, fastcoupling pressure test ports. The probe from the
differential pressure meter is inserted into the port packing, until the end of
the probe enters the system. When the measuring probe is pulled out, the
test port automatically closes, preventing uid leakage. Care should be taken
to pull the probe out slowly so as to allow adequate time for the packing to
re-seal – otherwise uid can quickly escape creating a hazardous situation.
Consult differential pressure meter manufacturer instructions for proper use
of instrument and pressure port couplings.
STATIC BALANCING VALVES, VARIABLE ORIFICE, FOR PLUMBING AND HYDRONICS
Memory stop feature.
Characterized plug for smooth adjustment.
Maximum working pressure: 232 psi.
Working temperature range: 14—250°F.
DZR low-lead brass body.
Meets requirements of NSF/ANSI 372-2011.
Complies with low lead laws and listed by
ICC-ES for use in accordance with the U.S.
and Canadian plumbing codes.
142
Flo-Set™ Variable Orifice
Insulation shell ts 142 series balancing
valves.
Code Description Lbs USD
CBN142241A fits ½" NPT 0.1
25.20
CBN142251A fits ¾" NPT 0.1 26.80
CBN142261A fits 1" NPT 0.1 36.50
CBN142271A fits 1¼" NPT 0.1 52.10
CBN142281A fits 1½" NPT 0.1 58.60
Code Description Max Cv Lbs USD
142241A ½" NPT female 3.4 1.0
98.00
142251A ¾" NPT female 5.0 1.2 104.50
142261A 1" NPT female 7.5 1.5 142.00
142271A 1¼" NPT female 12.9 2.3 203.00
142281A 1½" NPT female 16.8 3.0 227.00
142291A 2" NPT female 22.0 3.5 290.00
MEASURING
PROBE
SAFETY
CAP
SEAL
Operating Principal
The 142 series balancing valve is a hydraulic device that controls the ow rate
of a uid. Turning the knob moves a plug within the uid stream which varies
the ow rate. The ow rate is determined according to the pressure drop
value measured by a differential pressure meter connected to the pressure
test ports and the adjustment knob position.
Memory stop The 130 series balancing valve features a memory stop that
allows the valve to be reopened to the initial position if it has been closed for
any reason such as isolating components in the balanced circuit. Locking the
position to be memorized requires the use of a 2.5 mm hex key.
Adjustment knob The knob is made of a reinforced high strength corrosion-
resistant polymer. The shape of the knob is designed to ensure maximum
comfort for the operator and an accurate adjustment.
Adjustment reference scale Each 360° rotation of the knob moves the
turn indicator by one position, ranging from 0 (valve closed) to 4 (valve fully
open).