Brochure

67
6
B
Balancing valve with ow meter.
Direct reading of ow rate.
No sight gauge clouding or scaling.
Brass valve body and ow meter.
With insulation.
Max. working pressure: 150 psi.
Temperature range: 14—230°F.
Max. percentage of glycol: 50%.
132
QuickSetter
4
3
2
1
5
7
6
5
4
3
2
3
5
6
4
1
15
Operating principle
The balancing valve is a hydraulic device that controls the ow rate of the
heating/cooling transfer uid. The control mechanism is a ball valve (1),
operated by a control stem (2). The ow rate is manually and properly set by
use of the convenient onboard ow meter (3) housed in a bypass circuit on
the valve body. This circuit is automatically shut off during normal operation.
The ow rate is indicated by a metal ball (4) sliding inside a transparent
channel (5) with an integral graduated scale (6).
STATIC BALANCING VALVES WITH FLOWMETER FOR HYDRONICS
Code Description Flow scale (gpm) Lbs USD
132432A ½" FNPT 0.5—1.75 2.0 176.00
132436A ½" press 0.5 - 1.75 2.2 200.00
132552A ¾" FNPT 2.0—7.0 1.8 190.00
132556A ¾" press 2.0—7.0 2.0 214.00
132662A 1" FNPT 3.0—10.0 2.4 222.00
132666A 1" press 3.0—10.0 2.4 250.00
132772A 1¼" FNPT 5.0—19.0 2.8 295.00
132776A 1¼" press 5.0—19.0 2.8 332.00
132882A 1½" FNPT 8.0—32.0 3.4 350.00
132886A 1½" press 8.0—32.0 3.4 394.00
132992A 2" FNPT 12.0—50.0 4.4 427.00
132996A 2" press 12.0—50.0 4.4 482.00
Balancing valve with ow meter.
Direct reading of ow rate.
ANSI 125 anged cast iron body.
Brass ow meter.
Max. working pressure: 150 psi.
Temperature range: 14—230°F.
Max. percentage of glycol: 50%.
132
QuickSetter
Code Description Flow scale (gpm) Lbs USD
132060A 2½" ANSI flange 30—105 35
1,055.00
132080A 3" ANSI flange 38—148 62 1,408.00
132100A 4" ANSI flange 55—210 67 2,149.00
Code Description Lbs USD
F0000940 Replacement flowmeter 0.5 to 1.75 GPM 0.2 98.00
F0000941 Replacement flowmeter 2.0 to 7.0 GPM 0.2 98.00
F0000942 Replacement flowmeter 3.0 to 10 GPM 0.2 98.00
F0000943 Replacement flowmeter 5.0 to 19 GPM 0.2 102.70
F0000944 Replacement flowmeter 8.0 to 32 GPM 0.2 102.70
F0000945 Replacement flowmeter 12 to 50 GPM 0.2 102.70
F0000946 Replacement flowmeter 30 to 105GPM 0.2 108.00
F0000947 Replacement flowmeter 38 to 148 GPM 0.2 108.00
F0000948 Replacement flowmeter 55 to 210 GPM 0.2 108.00
F19346 Replacement by-pass valve stem* 0.2 35.70
Replacement flow meter.
Flow meter bypass valve
The bypass valve (1) opens and closes the circuit between the ow meter
and the valve. The bypass valve is easily opened by pulling the operating ring
(2), and is automatically closed by the internal return spring (3) when nished
reading the ow rate. The spring and the EPDM seal (4) provide a reliable
seal to isolate the ow meter during normal operation, protecting potential
debris from interfering with spring/magnetic disc mechanism. The operating
ring (2) material has low thermal conductivity to avoid burns if the ow meter
is opened while hot uid is passing through the valve.
1
234
4
6
7
5
Ball/magnet indicator
The metal ball (4) that indicates the ow rate
is not in direct contact with the heaing/cooling
transfer uid passing through the ow meter.
This is an effective and innovative measuring
system in which the ball slides up and down
inside a transpa ent channel (5) that is isolated
from the uid owing through the body of the
ow meter. The ball is moved by a magnet (6)
connected to a oat (7). In this way the ow
rate indication system remains perfectly clean
and provides reliable readings over time.
1
234
4
6
7
5
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
*With operating ring