Brochure
60
6
A
ELECTRONIC MIXING VALVE FOR PLUMBING
Electronic mixing valve with optional selectable programs for thermal disin-
fection of hot water recirculation system to kill Legionella bacteria.
Code number includes:
three-way ball valve
3-wire oating control actuator
controller/user interface with DIN rail mounting bracket
mixed outlet temperature sensor/probe
return temperature sensor/probe
mixed outlet temperature gauge
Power: 24 VAC +/- 10% - 50/60 Hz - 6 VA.
115/24 VAC transformer included.
Adjustment temperature range: 70 — 185
o
F.
Disinfection temperature range: 100 — 185
o
F.
Max body pressure rating (static): 230 psi.
Max operating pressure: 150 psi.
Max. inlet temperature: 212
o
F.
Protection class: IP 54 (controller).
Meets requirements of NSF/ANSI 372-2011 and complies with ASSE 1017,
CSA B125.3, UPC, IPC, Low Lead Laws and listed by ICC-ES
for use in accordance with the U.S. and Canadian plumbing codes.
Meets requirements of CSA Z317.1 Special Requirements For Plumbing
Installations In Health Care Facilities.
6000
LEGIOMIX
®
Function
The electronic mixing valve is used in centralized systems that produce
and distribute domestic hot water. The LEGIOMIX
®
electronic mixing valve
provides precise temperature control over very low and very high ow rate
demand, minimal pressure drop with a ball valve control element, automatic
self-cleaning to prevent scale formation and easy-to-use digital interface
with data logging, alarming and status indication.
Code Description Cv Lbs USD
600054A ¾" NPT male union 9.7 5.1 2,395.00
600059A ¾" sweat union 9.7 5.1 2,371.00
600056A ¾" press union 9.7 5.1 2,498.00
600064A 001 1" NPT male union, 3/4" body 9.7 5.3 2,515.00
600069A 001 1" sweat union, 3/4" body 9.7 5.3 2,498.00
600066A 001 1" press union, 3/4" body 9.7 5.2 2,592.00
600064A 1" NPT male union 21 7.3 2,633.00
600069A 1" sweat union 21 7.3 2,624.00
600066A 1" press union 21 7.3 2,687.00
600074A 1-1/4" NPT male union 24 8.2 2,715.00
600079A 1¼" sweat union 24 8.2 2,668.00
600076A 1¼" press union 24 8.2 2,734.00
600084A 1½" NPT male union 34 21 3,065.00
600089A 1½" sweat union 34 21 3,028.00
600086A 1½" press union 34 21 3,166.00
600094A 2" NPT male union 48 22 3,149.00
600099A 2" sweat union 48 22 3,106.00
600096A 2" press union 48 22 3,354.00
600060A 2½" ANSI 150 flanges 105 30 11,316.00
600080A 3" ANSI 150 flanges 120 42 11,978.00
°C
0
20
80
60
40
1
3
2
6
4
5
7
FRIDAY
T
M
077
•
F T
R
077
•
F
ADJUSTMENT
RUNNING
1) Legiomix digital regulator
2) Mixing valve
3) Mixing valve actuator
4) Mixed water flow probe
5) Return probe (recirculation)
6) Mixed water flow temperature gauge
7) Actuator fixing clip
1) LEGIOMIX
®
digital controller
2) Mixing valve
3) Mixing valve 24 V 3-wire floating actuator
4) Mixed outlet water temperature sensor
5) Return water (recirculation) temperature strap-on sensor.
6) Mixed outlet water temperature gauge
7) Actuator mounting clip
30
50
70
90
110
130
150
170
190
210
F
10/12/2017
+
-
Characteristic components
NEW
NEW
NEW
NEW
NEW
NEW
Recommended Flow Rates (gpm/lpm)
Size ¾” 1" 1¼" 1½" 2" 2½" 3"
Minimum ow* 2.2 / 8.3 3.1 / 11.7 4.4 / 16.6 6.6 / 25 8.8 / 33.3 17.0 / 64 22.0 / 83.3
Design ow** 27 / 102 58 / 220 66 / 250 93 / 352 131 / 495 288 / 1,090 329 / 1,245
Flow at 20 psid 43 / 172 94 / 356 107 / 405 152 / 575 215 / 814 470 / 1,780 537 / 2,033
Cv 9.7 21 24 34 48 105 120
*To ensure stable operation and ± 3º F accuracy. Minimum ow rate is 0 gpm when recirculation ow rate is greater than or equal to the valve size minimum ow rating.