User`s guide
54 — ElectriCalc Pro
NOTE: If a wire size has been calculated or
stored, and the wire type/quantity is not defined,
the calculator will assume 2 THHN wires for 1Ø
and 3 THHN wires for 3Ø when calculating
conduit size.
Finding Conduit Sizes for Multi-
ple Conductors — Same Wire
Type & Size
Find the minimum IMC conduit size for
eleven #6 THHN copper wires.
Steps Keystrokes Display
Clear calculator [On/C] [On/C] 0.
Enter cond. type 4 [Set] [CondSz] nonE
IMC
Enter wire size 6 [WireSz] 6 CU
AWG WIRE SIZE
Enter # THHN 11 [#THHN] 11.
THHN WIRES
Find conduit size [CondSz] 1.25 in
IMC COND SIZE
5060-UG-B-Composite 4/4/03 12:37 PM Page 56