Finding Derated Wire Size
What is the derated wire size required
for nine 75°C copper wires, each carry-
ing a maximum load of 65 amps?
Steps Keystrokes Display
Reset calculator [Set] [x] [On/C] 0.
Set to 75°C [Set] [7] 3Ø 75 Cu 0.
Enter amps 65 [Amps] 65. AMPS
Find normal
wire size [WireSz] 6 CU
AWG WIRE SIZE
Find derated
wire size 9 [Set] [ParSz] 3 CU
D/R WIRE SIZE