User`s guide
Pocket RefeRence Guide — 21
MOTOR FUNCTIONS
The ElectriCalc Pro can calculate 
the Full-Load Current (Amps) of a 
motor, based on Phase, Voltage and 
Motor (Synchronous, Induction, or 
DC) Horsepower using NEC Tables 
430.247, 430.248 and 430.250. 
Finding Full-Load Current
A 2 HP Induction motor operates on 
230 Volt, Single-Phase power. What is 
the Full-Load Current for this motor?
KEYSTROKE DISPLAY
   
0.
1. Set to 1-Phase:
 (1Ø) 1 Ø 
1  PH 
2. Enter Volts:
VOLT 230.
3. Enter HP:
IND* 2. HP 
* Press 
 until IND is displayed in the 
upper left area of the display.
4. Find Full-Load Current:
FLC 12.
 A 
Finding Motor Wire Size
Find the Wire Size required to connect 
a continuous run, 3Ø, 10 HP Induction 
motor into a 230V circuit.