Use and Care Manual
Po c k e t Re f e R e n c e Gu i d e — 25
(cont’d)
7. Set to 50º C Ambient Temperature:
(Ambº) Amb
AMB° 50. ºC
8. Find Derated Wire Size:
(D/R Size)
D/R 500 CU
WIRE SIZE
9. Reset Ambient Temperature
and Clear:
3Ø 60 Cu
0.
VOLTAGE DROP
The ElectriCalc Pro uses Resistance
values found in NEC Table 8 Chapter
9 to determine Voltage Drop, Wire
Lengths or Wire Sizes given a
maximum Voltage Drop percentage.
Finding Voltage Drop
You are installing 175 Feet of 75°C,
#8 THW branch circuit Copper
conductors to supply an 11A load on a
208V 1Ø system. What is the source
Voltage Drop at the load?
KEYSTROKE DISPLAY
0.
1. Set to 1-Phase:
(1Ø)
1 Ø
1 PH
2. Set to 75 º C:
(75º) 1 Ø 75
1 PH