Use and Care Guide

Pocket RefeRence Guide — 27
(cont’d)
3. Set to Copper (if necessary):
(Cu/Al)
75 Cu
3 PH
4. Enter Amps:

AMPS 20.
5. Enter Volts:

VOLT 208.
6. Enter Length:

FEET 175.
7. Enter allowable VD%:

DROP 3.0
%
V
8. Find Wire Size:
AWG 8 CU
VD WIRE SIZE
Finding Voltage Drop Distance
How far from a Three-Phase 240
Volt source can you install a 15 Amp
load using 60°C #10 Copper branch
circuit conductors? Assume a 3%
allowable Voltage Drop.
KEYSTROKE DISPLAY

0.
1. Set to 3-Phase:
(3Ø)
3 PH
2 Set to 60º C:
(60º)
3Ø 60
3 PH
3. Set to Copper (if necessary):
(Cu/Al)
60 Cu
3 PH