24 — ElectriCalc LT
Ampacity Wire Sizing
The required wire size of a service con-
ductor can be determined based on the
specified electrical requirements and
the [WireSz] key. The wire size is auto-
matically recalculated whenever the
wire insulation (temperature) ratings or
wire material (copper or aluminum)
types are revised. Wire sizing is based
on the requirements defined in NEC
Tables 310-16 and 310-17.
Wire Sizing Based
on Insulation Rating
Wiring is being installed in a 240 volt,
single-phase system rated at 30 kVA.
What is the wire size needed if you use
60°C copper wire?
Steps
Keystrokes
Display
Clear calculator [On/C] [On/C] 0.
Set to 1-phase [Set] 1 1 PH
Set to 60 [Set] 6 1Ø 60 Cu 1 PH
Enter kVA 30 [kilo-] [VA] 30. KVA
Enter volts 240 [Volts] 240. VOLT
Find amps [Amps] 125. AMPS
Find CU wire size [WireSz] 0 CU
AWG WIRE SIZE