Hardware manual
Appendix A
Modifying the TeleFlow Standard ACCOL (TSA) Load
TeleFlow
TM
Standard ACCOL Load and Menus
A-2
3 Analog Input Board with 1, 4,
5, or 8 points (or no board
installed)
AI1
AI4
AI5
AI8
4 High Speed Counter Board
with 1, 2, or 3 points (or no
board installed)
HSC1
HSC2
HSC3
5 Analog Output Board with 1
point (or no board installed)
AO1
Table 1-2 Communication Port Options
PORT Port Type Baud Rate Notes
A Pseudo Slave 300 - 38,400 Asynchronous
Local Port
B Slave 300 - 38,400 Asynchronous
Network Port
C Master 300 - 38,400 Asynchronous
Expanded I/O Port
NOTES ON POWER CONSUMPTION:
Assuming the Local Port is unused, the Network port is inactive, and the LCD
display is inactive, the 3530 will enter 'sleep' mode if it is not currently executing
an ACCOL task.
The larger the ACCOL load, the longer it takes to execute, and the longer the unit
'stays awake'. Load functions should be scheduled to run only when needed. This
means using logical signals as flags to control execution. Load tasks should be
carefully partitioned to execute only when necessary, so that maximum 'sleep' time
is obtained, thereby reducing power consumption.