Hardware manual

Chapter 2 - TeleFlow Standard ACCOL Load
TeleFlow 2-9 Standard ACCOL Load
Low-Flow Cut-OFF
The 'live' Differential pressure is always compared to a CUTOFF signal set in
inches of water. When the DP value drops below the value of the CUTOFF signal,
flow calculation will cease and the calculated flow-rate will be zero. Default cutoff is
0.25 inches of H
2
O.
Flow Time
While the DP is above the Cutoff limit the unit will accumulate a flow-time count
in minutes for the hour and day. In a backflow condition a separate backflow time
is accumulated.
Archive Files
Periodic Archive
The interval is 1 hour. At the end of the interval, the information shown below is
written into a periodic archive file. If log break is enabled, these values are written
when a configuration value changes.
DATE/TIME
LOCAL SEQUENCE NUMBER
GLOBAL SEQUENCE NUMBER
AVERAGE DP INH2O
AVERAGE STATIC PRESSURE PSIG
AVERAGE FLOWING TEMP. DEGF
FLOW TIME MINS
AVERAGE EXTENSION
ACCUMULATED VOLUME MSCF
ACCUMULATED ENERGY MMBTU
AVERAGE AUXILIARY INPUT %
Daily Archive
At the end of every day the information shown below is written into a daily archive