Specifications
61
Motor control
device
selection
Selecting
architecture:
The criteria described in chapter 2 were applied to build the communication architecture.
D.O.L. starter Soft starter VSD
Motor circuit
breaker +
Contactor
LC.D or F
Starter controller TeSys U Motor
management
system TeSys
T
ATS48 ATV31 ATV61
Standard
control unit
Advanced
control
unit
Multifunction
control unit
Type of links
Hard wired
Sand &
grease
removal
Modbus SL
Sand &
grease
removal
Lifting
CANopen
Ethernet Lifting
Advantys +
Pre wiring
Primary
clarier
Advantys
extension
bus
Screening Screening Screening
Advantys
CANopen
Sand &
grease
removal
The architecture proposed is consistent in terms of the communication solution and information monitoring.
It also shows different levels of architecture in term of cost and performance.
Water application example
Selection
DOL Soft
starter
VSD
Lifting Feed in pumps Redundant centrifugal pumps: Flow is controlled
by changing the speed of rotation in order to
better manage water ow variation.
ATV61
redun-
dant
Rain water
pumps
Centrifugal pumps: Flow is controlled easily by
valves on the pump discharge manifolds. The
rain water tank allows easy management of ow
variation.
ATS48
Screening Motor for scraper Motor for moving device. Constant and low
speed.
TeSys U
Motor for waste
compression
Motor to control valve with 2 positions. TeSys U
Motor for waste
evacuation
Motor for moving device with no speed
constraint.
TeSys U
Sand &
grease
removal
Air compressor The power required to manage an air
compressor can be signicant ( >15KW). For
this basin the requested pressure is constant.
TeSys T
Valve for sand
outlet
Valve with 2 positions with no specic con-
straint.
Contactor
LC.D or F
Motor for scraper Motor for moving device, with the possibility of
optimising the function
ATV31
Motor for the
shield
Motor to control the shield. No specic con-
straint linked to this equipment.
TeSys U
Pump to extract
the sand
Redundant pumps to ensure sand extraction in
the event of a fault
TeSys U
LC.D or F
Primary
clarier
Motor for scraper Motor for moving device. Constant and low
speed.
TeSys U
Motor for the
shield
Motor to control the shield. No specic
constraint linked to this equipment.
TeSys U
Valve for sand
outlet
Valve with 2 positions with no specic constraint Contactor
LC.D or F
The following table describes the selection criteria used to select the most appropriate motor control devices.