HMI_MOTOR_TU_x (x=s for Standard, x=a for Advanced, x=m for Multi-function)
Auto_Man Bool Command to set the block in Auto or Manu
Run_Stop Bool Command to run or stop the pump
Clear_Fault Bool Command to acknowledge internal and external errors indicated at the
output Error. Acknowledgement is done with a rising edge.
Clear_Warning Command to acknowledge starter warning. Acknowledgement is done
with a rising edge.
Meas_1 (1),(2) Int Average motor current in % of FLA.
Nb_start Int Number of starts performed in the last 24 hours, displayed on HMI
(calculated value)
Min_time_stop Int Minimum time between stop and start
Discrepancy_time Int Maximum time between and order and the right feedback
Time_to_start Dint Time before the motor restart, calculated when
Param_Min_time_stop<>0.
Sts_Auto Bool Automatic mode is activated. The process sequence manages the motor
Sts_Manual Bool Manual mode is activated. The commands come from HMI or SCADA.
Sts_Local Bool Local mode is activated. The commands are hardwired.
Sts_Off Bool The TeSys is powered off by the hardwired.
Sts_Discrepancy_Err Bool Discrepancy error. The discrepancy control is activated
( Discrepancy_time<>0 ).
Sts_Error Bool Indicates that the operation is blocked by an internal or external
(Input Err) error, which is not acknowledged.
Sts_TimerProtect Bool Number start control is activated (Nb_start_day <>0) and the max starts
number is reached.
Sts_Ready Bool TeSys-U ready to switch on
Sts_Run Bool The motor is running (Status from starter)
Sts_ExtErr Bool External error from the process or the system
Sts_Tsys_Fault Bool TeSys U all fault
Sts_Tsys_Rst_Auth Bool Reset TeSys fault authorized
Sts_Tsys_Warning Bool TeSys U all fault
W_Thermal (1), (2) Bool Thermal warning
W_Module (1), (2) Bool Module warning
Sts_Butt_On (2) Bool Button ON
Sts_Butt_On (2) Bool Button TRIP
Sts_Tsys_Closed (2) Bool Poles closed
Name String[10] Motor name & location
The table below details the interface between the starter and the DFB into PLC application I/O Interface, Inputs
and output words are exchanged according to the table below
Type Number Comment
DI 2 Operating mode selector switch in “Remote” position.
Operating mode selector switch in “Local” position.
DO 2 Auto mode indicator light
Fault light
AI - Spare
AO - Spare
TeSys U
controler DFB
(cont’d)
Note: The specic features relating to Advanced unit control are marked (1) and relating to Multi-function unit
control are marked (2).
5-Implementation
PLC and motor control device implementation