TeSys U
controler
This section describes three references of TeSys_U control unit (Standard, Advanced, Multi-function), connected
between STB main rack and STB extension rack.
An Ethernet IO scanning service is used to periodically exchange data between the PLC and the motor starter.
For TeSys_U behind an Advantys STB island, the STB island I/O mapping is used.
The table below details the interface between the starter and the DFB into PLC application.
TeSys U UNITY PLC
Register Description Located @
%MW
Variable (DDT) DFB pin
455 State register %MWx TeSysUs_IO_SCAN_I
(1) TeSysUa_IO_SCAN_I
(2) TeSysUm_IO_SCAN_I
FbStat
FbStat
FbStat
FbStat
458 I/O status register %MWx+1
461 (1) (2) Warning register %MWx+2
457 (2) Mechanical & power supply
status register
%MWx+3
704 Control Register %MWy TeSysU_IO_SCAN_O QCtrl
703 Control of communication
module
%MWy+1 TeSysU_IO_SCAN_O
700 Output control %MWy+2 TeSysU_IO_SCAN_O
Note: The specic features relating to Advanced unit control are marked (1) and relating to Multi-function unit
control are marked (2)
x=rst input register, y=rst output register (for more details see TeSys U conguration example in chapter 4)
5-Implementation
PLC and motor control device implementation
Pin
-Interface Type MOT_TeSysU Type -Interface
1
Variable (IO_PLC) Bool Local FbAuto Bool Variable (DDT)
2
Variable (IO_PLC) Bool Remote FbManual Bool Variable (DDT)
FbLocal Bool Variable (DDT)
FbOff Bool Variable (DDT)
6
Variable (DDT) Bool Arun FbRun Bool Variable (DDT)
7
Variable (DDT) Bool Lock Locked Bool Variable (DDT)
8
Variable (DDT) Bool ExtErr Error Bool Variable (DDT)
Warning Bool Variable (DDT)
Ave_Cur Int Variable (DDT)
13
Variable (IO_PLC) Int* FbStat QCtrl Int* Variable (IO_PLC)
16 Variable (DDT) Pump_Param
Param
17
(HMI) HMI_MOTOR_x HMI HMI
(*) These variables are from the TeSysU_IO_SCAN structure (see description in the table below).
Input description
FbStat TeSys_U status words.
Output description
Av_Cur (1), (2) Average motor current in % of FLA.
QCrtl Starter control word, sent to the starter via I/O scanning
In-output description
(HMI) Structure with command from HMI or SCADA and feedback to HMI or SCADA
DFB behaviour is compliant with the previous description (see page25),
TeSys U
controler DFB