Specifications

49
PROTECTED TYPED LOGICAL READ/WRITE WITH 3 ADDRESS FIELDS
[CMD,FNC,FILE#,FILETYPE] = [0F,A2,07,89] (READ N7 REGISTERS)
REGISTERS DESCRIPTORS
N7:0-1* METER 1 TOTAL (UNSCALED)
N7:2-3* METER 2 TOTAL (UNSCALED)
N7:4-5** FLOW 1 X 1000
N7:6-7** FLOW 2 X 1000
N7:8 ROLLOVERS – METER 1
N7:9 ROLLOVERS – METER 2
N7:10 AIN 1 (0-10000)
N7:11 AIN 2 (0-10000)
N7:12 SUPPLY VOLTS X 10
N7:13 AUXILIARY DIGITAL I/O 1
N7:14 AUXILIARY DIGITAL I/O 2
N7:15 METER 1 READ FAULT
N7:16 METER 2 READ FAULT
N7:17-18* SYSTEM UPTIME (MINUTES)
N7:19 METER 1 nDIGITS
N7:20 METER 2 nDIGITS
N7:21 METER 1 EXPONENT
N7:22 METER 2 EXPONENT
N7:23 METER 1 UNITS
N7:24 METER 2 UNITS
N7:25 METER 1 READ FAULT COUNTER
N7:26 METER 2 READ FAULT COUNTER
N7:27 METER 1 FLOW CALC METHOD
N7:28 METER 2 FLOW CALC METHOD
N7:29 METER 1 SAMPLE PERIOD (SECS)
N7:30 METER 2 SAMPLE PERIOD (SECS)
N7:31 METER 1 FLOW TIMEOUT (SECS)
N7:32 METER 2 FLOW TIMEOUT (SECS)
N7:33 METER 1 POWERUP (MSECS)
N7:34 METER 2 POWERUP (MSECS)
N7:35 METER 1 PROTOCOL (1=SENSUS,2=NEPTUNE)
N7:36 METER 2 PROTOCOL (1=SENSUS,2=NEPTUNE)
N7:37 COMPOUNDED METER EXPONENT (COMP EXP)
N7:38-39* METER 1 UPPER TOTAL (ACTUAL / 10
(COMP EXP)
)
N7:40-41* METER 2 UPPER TOTAL (ACTUAL / 10
(COMP EXP)
)
N7:42-43* COMPOUND METER UPPER TOTAL (ACTUAL / 10
(COMP EXP)
)
N7:44 METER 1 LOWER TOTAL (ACTUAL % 10
(COMP EXP)
)
N7:45 METER 2 LOWER TOTAL (ACTUAL % 10
(COMP EXP)
)
N7:46 COMPOUND METER LOWER TOTAL (ACTUAL % 10
(COMP EXP)
)
N7:47-48** COMPOUND FLOW X 1000
*DATA OCCUPYING THESE REGISTERS ARE 32-BIT UNSIGNED LONG INTEGERS.
**DATA OCCUPYING THESE REGISTERS ARE 32-BIT SIGNED LONG INTEGERS.
ALL OTHERS ARE 16-BIT SIGNED INTEGERS
[CMD,FNC,FILE#,FILETYPE] = [0F,A2,FA,85] (READ B250 REGISTERS)
INPUTS DESCRIPTORS
B250:0/0 AUXILIARY DIGITAL I/O 1
B250:0/1 AUXILIARY DIGITAL I/O 2
B250:0/2 METER 1 READ FAULT
B250:0/3 METER 2 READ FAULT
B250:0/4 METER 1 FORWARD FLOW (Y/N)
B250:0/5 METER 2 FORWARD FLOW (Y/N)
B250:0/6 METER 1 REVERSE FLOW (Y/N)
B250:0/7 METER 2 REVERSE FLOW (Y/N)
[CMD,FNC,FILE#,FILETYPE] = [0F,AA,0A,85] (WRITE B10 REGISTERS)
B10:0/0 AUXILIARY DIGITAL OUTPUT 1
B10:0/1 AUXILIARY DIGITAL OUTPUT 2
EtherMeter N-File, B-File Register Map.