Specifications

12
Neptune
(Schlumberger)
E-Coder™
Compatible (based upon laboratory and/or field testing).
Test Registers provided courtesy of Neptune Technology Group.
Excellent
register for SCADA System interrogation of encoder register.
Provides high-resolution totalization (8 digits).
The high-resolution totalization speeds the flow-rate calculation and detection of
reverse flows.
Does not contain or require a battery, as it draws its power from the interrogation
device.
Can be interrogated every 8 seconds (328,500 times per month), with no apparent
wear.
Register does not require any special factory pre-programming (Factory Defaults =
OK).
Wiring Color Codes: BLACK=TX, RED=RX, GREEN=CMN
Neptune
(Schlumberger)
ProRead™
“Auto”
Compatible (based upon laboratory and/or field testing).
Test Registers provided courtesy of Neptune Technology Group.
Fair
register for SCADA System interrogation of encoder register.
Provides low/medium-resolution totalization (5.2 digits).
The low/medium-resolution totalization delays flow-rate calculations and reverse-flow
detection. (The “FIXED DTOTAL” flow calculation method is recommended.)
Does not contain or require a battery, as it draws its power from the interrogation
device.
Can be interrogated every 8 seconds (328,500 times per month), with no apparent
wear.
Register requires factory pre-programming. The maximum (5.2 digits) is
recommended.
Wiring Color Codes: BLACK=TX, RED=RX, GREEN=CMN
Sensus
(Rockwell/
Invensys)
ICE
®
(ECR-III)
Compatible (based upon laboratory and/or field testing).
Test Registers provided courtesy of Sensus Metering Systems.
Excellent
register for SCADA System interrogation of encoder register.
Provides high-resolution totalization (8 digits).
The high-resolution totalization speeds the flow-rate calculation and detection of
reverse flows.
Does not contain or require a battery, as it draws its power from the interrogation
device.
Can be interrogated every 8 seconds (328,500 times per month), with no apparent
wear.
Register requires factory pre-programming. The maximum (8 digits) is
recommended.
Wiring Color Codes: RED=TX, GREEN=RX, BLACK=CMN