Warranty

Installation / Assembly
11
Fire Pit Owner’s Manual
LTR50001010, Rev. C
2) All sides are completely enclosed.
This method requires at least two ventilation openings at cylinder valve
level in the side wall, equally sized, spaced at 180 degrees (3.14 rad),
and unobstructed.
Make sure each opening has a
total free area of not less then
½ square inch per pound (3.2
sq. cm/kg) of stored fuel capac-
ity and not less then a total free
area of 10 square inches (64.5
sq. cm).
Ventilation openings need to
be provided at oor level with
a total free area of ½ inch per
pound (3.2 sq. cm/k) of stored
fuel capacity and not less than
a total free area of 10 square
inches if the ventilation open-
ings at oor level are in a side
wall, make sure there are at
least two openings. The bottom
of the openings shall be at oor level and the upper edge no more than
5 inches (127 mm) above the oor. The openings need to be equally
sized, spaced at 180 degrees (3014 rad) and unobstructed.
Make sure every opening has minimum dimensions to permit the en-
trance of a 1/8 inch (3.2mm) diameter rod.
There shall be a minimum clearance of 2 inches (40.8mm) between the
lower surface of the oor and the propane gas supply cylinder enclo-
sure and the ground.
W
ID
T
H
W
ID
T
H
DEPTH
HEIGHT
Screen vents
One side openOne side open