Specifications
Page 72 of 76 SmartSource 2-Stage Water Source Heat Pumps Catalog 1114-1
Engineering Guide Specications
WallMountedRoomTemperatureSensors:
• Digitally Adjustable Wall Sensor with Temperature and Humidity Display
• Adjustable Cool/Warm with Occupancy Switch, Override/Reset Button, Status LED, Fan and System Switch
• Adjustable 55° to 95°F and 12° to 33°C, Override/Reset Button, Status LED, Fan and System Switch
• Adjustable -5°F to +5°F and -20°C to -15°C, Override/Reset Button, Status LED, Fan and System Switch
• Basic Sensor, Override/Reset Button, Status LED
Humidistat
To be used in conjunction with one of the dehumidication options. Humidistat to be wall mounted and capable of providing
solid state input to unit controls to enable/disable dehumidication features.
Hose Kits
Two re-rated exible hoses with ASTM ratings of Flame Spread 25, Fuel Contribution 25 and Smoke Density 50 for con-
nection to unit and eld piping. Hose shall be covered with stainless steel braiding to prevent damage.
Condensate Hose Kits
• Optional plastic hose including ttings
• Optional re-rated, braided steel hose including ttings
Valve Options
• Optional 2-way, Normally Open (N.O.) or Normally Closed (N.C.) motorized valves.
• Optional 2-way, mechanical ball valve
Automatic Flow Hose Kit
The automatic ow hose kit shall include an automatic ow control valve, two ball valves, two exible hoses, a high ow
Y-strainer, and may include a strainer blow-down and various other accessories. The automatic ow control valve shall be
factory set to a rated ow, and shall automatically control the ow to within 10% of the rated value over a 40 to 1 differen-
tial pressure, operating range (2 to 80 PSID). Operational temperature shall be rated from uid freezing, to 225°F. The valve
body shall be constructed from hot forged brass UNS C37700 per ASTM B-283 latest revision.
Stand for Vertical Units
A steel, corrosion resistant stand shall be offered to be used to raise the vertical WSHP’s above oor level. Height shall be
xed and not selectable.
Replacement Filters
2-inch MERV 8, 4 inch MERV 13, and 2-inch disposable lters shall be available as direct replacement to factory-installed lters.
Electric Heat Coils
An optional 5, 10, 15, or 20 kW eld installed duct heater shall be available. These heaters will require a eld provided power
source. 15 and 20 kW heaters shall be 2-stage.
Appendix-A
Capacity table legend:
Btu/hr = British Thermal Units per Hour
CFM = Airow Rate, Cubic Feet per Minute
COP = Coefcient of Performance
EAT = Entering Air Temperature
EER = Energy Efciency Ratio
EWT = Entering Water Temperature
Ft of W.C. = Feet of Water Column
GPM = Gallons per Minute
kW = Kilowatts
LAT = Leaving Air Temperature
PSI = Pounds per Square Inch
THA = Total Heat of Absorption
THR = Total Heat of Rejection
WPD = Waterside Pressure Drop
◄ BACK TO "Capacity Data – Size 026 (800 CFM)" on page 36 .
Appendix-B
Note: ECM motors on 460/60/3 volt units require a 265 volt power supply. Both a hot AND a neutral wire are required to
obtain proper fan motor voltage. Therefore, 4-wires with a wye type wiring arrangement is required.