Specifications

Catalog 1114-1 SmartSource 2-Stage Water Source Heat Pumps Page 55 of 76
Electrical Data
Table25:Standardunitwithoutoptions
Unit
Size
Rated Voltage
Minimum
Voltage
Compressor
Fan
Motor FLA
Total Unit
FLA
Minimum
Circuit
Amps
Maximum Fuse or
HACR Breaker Size
Voltage RLA LRA
026
208-230/60/1 197 11.7 58.3 3.0 14.7 17.6 25
265/60/1 239 9.1 54.0 2.6 11.7 14.0 20
208-230/60/3 197 6.5 55.4 3.0 9.5 11.1 15
*460/60/3 414 3.5 28.0 2.6 6.1 7.0 15
032
208-230/60/1
197
13.1 73.0 5.0 18.1 21.4 30
265/60/1
239
10.2 60.0 4.1 14.3 16.9 25
208-230/60/3
197
8.7 58.0 5.0 13.7 15.9 20
*460/60/3
414
4.3 28.0 4.1 8.4 9.5 15
038
208-230/60/1
197
15.3 83.0 5.0 20.3 24.1 35
208-230/60/3
197
11.6 73.0 5.0 16.6 19.5 30
*460/60/3
414
5.7 38.0 4.1 9.8 11.2 15
044
208-230/60/1
197
17.9 96.0 7.3 25.2 29.7 45
208-230/60/3
197
14.2 88.0 7.3 21.5 25.1 35
*460/60/3
414
6.2 44.0 5.5 11.7 13.3 15
049
208-230/60/1
197
21.2 104.0 7.3 28.5 33.8 50
208-230/60/3
197
14.0 83.1 7.3 21.3 24.8 35
*460/60/3
414
6.4 41.0 5.5 11.9 13.5 15
064
208-230/60/1
197
27.1 152.9 9.4 36.5 43.3 60
208-230/60/3
197
16.5 110.0 9.4 25.9 30.0 45
*460/60/3
414
7.2 52.0 6.9 14.1 15.9 20
072
208-230/60/1
197
29.7 179.2 9.4 39.1 46.5 60
208-230/60/3
197
17.6 136.0 9.4 27.0 31.4 45
*460/60/3
414
8.5 66.1 6.9 15.4 17.5 25
Notes: Electrical data for units with loop pumps, electric heat and other options is available from the Daikin McQuay
SelectTools™ software selection program for Water Source Heat Pumps. Consult your local Daikin McQuay
representative for further information. *All 460/60/3 units require 4-wire power which includes a neutral wire. See
"Appendix-B" on page 72.
Table26:Electricheatavailability
Single Power Point Dual Power Point
Model
Nominal
Capacity
Unit
Voltage
Electric Heat
Secondary
Heat Control
Electric Heat
Secondary
Heat Control
Electric Heatt
Secondary
Heat Control
5kW 10kW 5kW 10kW 15kW 20kW
GTH &
GTV
026
208-230/60/1 B,E,P S
265/60/1 B,E,P S
208-230/60/3 B,E,P S
460/60/3 B,E,P S
032
208-230/60/1 B,E,P S
265/60/1 B,E,P S
208-230/60/3 B,E,P S
460/60/3 B,E,P S
038
208-230/60/1 B,E,P S B,E,P,S
208-230/60/3 B,E,P S B,E,P,S
460/60/3 B,E,P S B,E,P,S
044
208-230/60/1 B,E,P S B,E,P,S
208-230/60/3 B,E,P S
460/60/3 B,E,P S B,E,P,S
049
208-230/60/1
B,E,P S B,E,P,S
208-230/60/3 B,E,P S
460/60/3 B,E,P S B,E,P,S
064
208-230/60/1 B,E,P S B,E,P,S
208-230/60/3 B,E,P S
460/60/3 B,E,P S B,E,P,S
072
208-230/60/1 B,E,P S B,E,P,S
208-230/60/3 B,E,P S
460/60/3 B,E,P S B,E,P,S
Legend: B = Boilerless, E = Emergency, P = Primary, S = Supplemental