Product Data 48HJD,HJF015-025 50HJ015-025 Single Package Rooftop Units 12 to 20 Nominal Tons 48/50HJ015,017 High Performance, Single Package Rooftop Units with: • Cooling EERs up to 10.
Durable, dependable construction Designed for durability in any climate, the weather-resistant cabinets are constructed of galvanized steel, bonderized, and all exterior panels are coated with a prepainted baked enamel finish. The paint finish is non-chalking, and is capable of withstanding ASTM B117 500-hour Salt Spray Test. All internal cabinet panels are primed, permitting longer life and a more attractive appearance for the entire unit.
Features/Benefits (cont) For units without economizer, yearround ventilation is enhanced by a manual outdoor-air damper. The damper can be preset to admit up to 25% outdoor air. In addition, the barometric relief damper or power exhaust accessory can be utilized to help maintain proper building pressure. Quiet, efficient operation and dependable performance Scroll compressors have vibration isolators for extremely quiet operation. Efficient fan and motor design permits operation at very low sound levels.
Features/Benefits (cont) various panels. Each hinged panel is permanently mounted to the unit, thereby eliminating the concern of a dropped or wind-blown panel puncturing delicate roof materials. The 4 extended access panels are also equipped with ‘‘tie back’’ retaining devices to hold the door in the open position while servicing the unit.
ARI* capacity ratings UNIT 48HJD NOMINAL TONS STANDARD CFM 015 017 025 12 15 20 3600 5300 6100 UNIT 48HJF NOMINAL TONS STANDARD CFM 015 017 025 12 15 20 3600 5300 6100 UNIT 50HJ NOMINAL TONS STANDARD CFM 015 017 025 12 15 20 3600 5300 6100 Bels db EER IPLV wb — — — — — NET COOLING CAPACITY (Btuh) 134,000 180,000 232,000 NET COOLING CAPACITY (Btuh) 134,000 180,000 232,000 NET COOLING CAPACITY (Btuh) 134,000 180,000 234,000 TOTAL WATTS EER 12,209 17,064 24,847 10.60 10.50 9.
ARI capacity ratings (cont) COOLING OPERATION AIR QUANTITY LIMITS UNIT 50HJ 015 017 025 MINIMUM CFM 3600 4500 6000 MAXIMUM CFM 6,250 7,500 10,000 OUTDOOR AIR LOW TEMPERATURE OPERATING LIMITS UNIT SIZE Standard Unit 40 40 015, 017 025 TEMPERATURE LIMIT (F) Unit With Unit With Low Ambient Kit Motormaster 20 –20 25 –20 MULTIPLICATION FACTORS HEATER RATING VOLTAGE 240 480 600 200 0.694 — — 208 0.751 — — 230 0.918 — — 240 1.000 — — ACTUAL HEATER VOLTAGE 380 440 460 — — — 0.626 0.840 0.
OUTDOOR SOUND POWER 48/50HJ RATING (Bels) A-WEIGHT (dB) 015,017 025 8.8 9.4 87.6 94.4 63 90.8 99.7 125 88.7 93.0 250 86.4 93.7 OCTAVE BANDS 500 1000 84.3 83.5 91.8 89.7 2000 78.4 85.9 4000 75.6 80.7 8000 66.8 74.7 LEGEND Bels — Sound Levels (1 bel = 10 decibels) INDOOR SOUND DATA (TOTAL UNIT) UNIT 48/50HJ SOUND RATING-BELS (60 Hz) A-WEIGHTED (dB) 015 017 025 8.8 8.9 9.5 87.3 88.0 94.1 63 87.1 95.7 90.6 125 89.9 88.9 87.2 250 86.4 87.2 89.
Physical data PHYSICAL DATA — 48HJ UNITS UNIT 48HJD/F NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* Economizer Roof Curb† MoistureMi$er Dehumidification Package COMPRESSOR Quantity...Model (Ckt 1, Ckt 2) Number of Refrigerant Circuits Loading (% of full capacity) Crankcase Heater Watts Oil (oz) (Ckt 1, Ckt 2) REFRIGERANT TYPE Expansion Device Operating Charge (lb) Circuit 1** Circuit 2 CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...
PHYSICAL DATA — 50HJ UNITS UNIT 50HJ UNIT VOLTAGE NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* Economizer Roof Curb† MoistureMi$er Dehumidification Package COMPRESSOR Quantity...Model (Ckt 1, Ckt 2) Number of Refrigerant Circuits Loading (% of full capacity) Oil (oz) (Ckt 1, Ckt 2) REFRIGERANT TYPE Expansion Device Operating Charge (lb)** Circuit 1 Circuit 2 208/230 CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.
Physical data (cont) OPERATING AND RIGGING WEIGHTS UNIT BASE UNIT OPERATING WEIGHTS* 017 lb kg 1800 816 1650 748 015 lb 1725 1575 48HJD/F 50HJ kg 782 714 025 lb 1900 1750 kg 862 794 *Base unit weight does not include electric heaters, copper coils, economizer, power exhaust, barometric relief or crating. See Options and Accessories table below for more information. NOTE: For 015 and 017 unit sizes add 75 lb (34 kg) for domestic crating. For 025 unit sizes add 135 lb (61 kg).
Options and accessories ITEM MoistureMi$er Dehumidification Package Apollo Direct Digital Communicating Controls Service Options (sold separately) 115 v Outlet Non-Fused Disconnect Hinged Access Panels Integrated Economizer Electric Heat (50HJ Only)** Enviro-Shield™ Condenser Coil Options Hail Guard Condenser Coil Grille Alternate Drive Hail Guard Double Wall Construction UVC Lamps Novar Controls Johnson METYSES Controls Stainless Steel Condensate Pan Service Valves Stainless Steel Heat Exchangers LP (Liqui
Options and accessories (cont) FACTORY-INSTALLED APOLLO COMMUNICATING CONTROLS ACCUSENSOR™ III (Enthalpy and Differential Enthalpy Control) + The Apollo direct digital controls are designed exclusively by Carrier, and are used to actively monitor and control all modes of operation as well as to monitor evaporator-fan status, filter status, supply-air temperature, outdoor-air temperature, and indoor-air quality.
BAROMETRIC RELIEF/POWER EXHAUST ELECTRIC HEATERS (50HJ Units Only) When used with accessory/optional economizer, the barometric relief or power exhaust accessory helps to relieve building overpressurization. NOTE: This is not available to be installed on a unit with horizontal supply adapter curb. However, the accessory may be installed in the return ductwork. Electric heaters (and single point kits) are available in a wide range of capacities for factory or field installation.
Options and accessories (cont) SERVICE OPTIONS UNIT MOUNTED DISCONNECT HINGED ACCESS PANELS Factory-installed, internally-mounted, NEC (National Electrical Code) and UL (Underwriters’ Laboratories) approved nonfused switch provides unit power shutoff with disconnect lockout protection capability. The control box access door is interlocked with the non-fused disconnect. The non-fused disconnect must be in the OFF position to open this door. The switch is accessible from outside the unit.
HUMIDISTAT MOISTUREMISER % RELATIVE HUMIDITY Field-installed, wall-mounted humidistat is used to control operation of the MoistureMi$er dehumidification package. The humidistat controls the occupied space humidity at a user-selected setting between 20% and 80% relative humidity. MOISTUREMI$ER DEHUMIDIFICATION PACKAGE The MoistureMi$er dehumidification package is a factory-installed option that provides increased dehumidification by cooling the hot liquid refrigerant leaving the condenser coil.
48HJD, HJF015 48HJD, HJF017 UNIT 782 816 1725 1800 STD UNIT WEIGHT Lb Kg 110 110 50 50 ECONOMIZER WEIGHT Lb Kg 417 407 189 185 CORNER A Lb Kg 181 170 481 383 218 174 CORNER C Lb Kg 503 410 228 186 CORNER D Lb Kg 3- 2 3-3 961 991 mm DIM A ft-in. 3-6 3- 5 Direction of airflow. Center of Gravity. 1-10 1-10 559 559 mm DIM C ft-in. 5. Ductwork to be attached to accessory roof curb only. 6. Minimum clearance: • Rear: 7′-0″ (2134) for coil removal.
110 lbs (50 kg) 1900 lbs (862 kg) Direction of airflow. Center of Gravity. 5. Ductwork to be attached to accessory roof curb only. 6. Minimum clearance: • Rear: 7′-0″ (2134) for coil removal. This dimension can be reduced to 4′-0″ (1219) if conditions permit coil removal from the top. • 4′-0″ (1219) to combustible surfaces, all four sides (includes between units). • Left side: 4′-0″ (1219) for proper condenser coil airflow. • Front: 4′-0″ (1219) for control box access.
50HJ015 50HJ017 UNIT STD UNIT WEIGHT Lb Kg 1575 714 1650 748 ECONOMIZER WEIGHT Lb Kg 110 50 110 50 CORNER A Lb Kg 407 185 375 170 CORNER C Lb Kg 383 174 449 204 CORNER D Lb Kg 410 186 452 205 mm 1039 963 DIM A ft-in. 3-5 3-2 Direction of airflow. Center of Gravity. mm 559 559 DIM C ft-in. 1-10 1-10 5. Ductwork to be attached to accessory roof curb only. 6. Minimum clearance: • Rear: 7′-0″ (2134) for coil removal.
50HJ025 UNIT STD UNIT WEIGHT Lb Kg 1750 794 ECONOMIZER WEIGHT Lb Kg 110 50 CORNER A Lb Kg 420 191 CORNER B Lb Kg 395 179 CORNER D Lb Kg 486 221 mm 988 DIM A ft-in. 3-3 mm 1054 DIM B ft-in. 3-5 Direction of airflow. Center of Gravity. 5. Ductwork to be attached to accessory roof curb only. 6. Minimum clearance: • Rear: 7′-0″ (2134) for coil removal. This dimension can be reduced to 4′-0″ (1219) if conditions permit coil removal from the top.
CURB HEIGHT 1′−2″ (305) 2′-0″ (610) 2′-0″ (610) CRRFCURB010A00 CRRFCURB011A00 CRRFCURB012A00 PKG. NO. REF. Standard Curb 14″ High Standard Curb for Units Requiring High Installation Side Supply and Return Curb for High Installation DESCRIPTION Direction of airflow. ALL UNIT in. .45 Deg. .28 A .28 Deg. B DIMENSIONS* (degrees and inches) .43 in. 5. Roof curb: 16 ga. (VA03-56) stl. 6.
HORIZONTAL SUPPLY/RETURN ADAPTER INSTALLATION NOTE: CRRFCURB013A00 is a fully factory preassembled horizontal adapter and includes an insulated high static regain transition duct which substantially improves fan static performance. The Barometric Relief Damper and Power Exhaust accessories are not available with the horizontal adapter. ACCESSORY PACKAGE NO.
Accessory dimensions (cont) FACTORY-INSTALLED CONVENIENCE OUTLET FACTORY-INSTALLED NON-FUSED DISCONNECT COMPRESSOR SECTION DOOR TOP CONTROL BOX SECTION DOOR DISCONNECT HANDLE 2'-5 1/4" (743) FRONT VIEW 22 1'-1 11/16" (347)
Selection procedure (with 48HJ025 example) I. Determine cooling and heating requirements at design conditions. Given: Required Gross Cooling Capacity (TC) . . . . . . . . . . . . . . .216,000 Btuh Gross Sensible Heat Capacity (SHC) . . . . . . . . . . . . . .168,000 Btuh Required Heating Capacity . . . . . . .190,000 Btuh Condenser Entering Air Temperature . . . . . . . . . . . . . . . . 95 F Summer Indoor Air Temperature . . . . . . 80 F edb, 67 F ewb Evaporator Air Quantity. . . . . . . . . . . .
Selection procedure (with 50HJ017 example) I. Determine cooling and heating requirements at design conditions. Given: Required Gross Cooling Capacity (TC) . . . . . . . . . . . . . . .168,000 Btuh Gross Sensible Heat Capacity (SHC) . . . . . . . . . . . . . .121,000 Btuh Required Heating Capacity . . . . . . .110,000 Btuh Condenser Entering Air Temperature . . . . . . . 95F Indoor Air Temperature . . . . . . 80 F edb, 67 F ewb Evaporator Air Quantity. . . . . . . . . . . .
Performance data COOLING CAPACITIES 48/50HJ015 (12 TONS) Temp (F) Air Entering (Edb 75 85 95 105 115 117 120 125 TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 3600/0.03 62 134 111 7.9 130 109 8.9 125 106 9.9 120 104 11.1 114 100 12.3 108 98 13.6 112 100 12.9 109 98 13.6 67 145 93 8.1 140 90 9.1 134 87 10.1 129 85 11.2 122 81 12.5 115 78 13.8 119 80 13.1 115 79 13.8 4375/0.04 72 153 72 8.2 147 68 9.2 141 66 10.2 134 63 11.3 127 60 12.6 118 57 13.9 123 59 13.2 118 57 13.
Performance data (cont) COOLING CAPACITIES (cont) 48/50HJ025 (20 TONS) Temp (F) Air Entering Condenser (Edb) 75 85 95 105 115 125 BF — Edb — Ewb — kW — ldb — lwb — SHC — TC — TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW TC SHC kW 6000/0.04 62 238 198 15.7 231 194 17.0 222 189 18.3 211 185 19.7 202 180 21.2 191 175 22.7 67 260 166 16.3 252 163 17.6 242 159 18.9 231 155 20.3 220 151 21.8 208 146 23.3 7000/0.05 72 283 134 16.9 274 131 18.2 264 127 19.6 252 123 21.0 241 119 22.5 227 115 23.
COOLING CAPACITIES (cont) 48/50HJ015 (12 TONS) UNITS WITH MOISTUREMI$ER OPTION Evaporator Air Quantity — Cfm/BF Temp (F) 3600/0.03 4375/0.04 5000/0.05045 5625/0.06 Air Entering Condenser Evaporator Air — Ewb (F) (Edb) 62 67 72 62 67 72 62 67 72 62 67 72 — 139 153 130 144 153 135 145 155 138 147 159 TC 75 — 81 63 111 93 68 118 98 68 125 104 72 SHC — 8.0 8.2 7.9 8.3 8.2 7.9 8.1 8.3 8.0 8.2 8.3 kW — 133 142 125 137 146 129 138 146 132 140 148 TC 85 — 75 56 105 84 61 113 93 62 120 98 66 SHC — 8.9 9.1 8.8 9.2 9.
Performance data (cont) COOLING CAPACITIES (cont) 48/50HJ025 (20 TONS) UNITS WITH MOISTUREMI$ER OPTION Evaporator Air Quantity — Cfm/BF Temp (F) 5700/0.03 6650/0.05 7600/0.06 8550/0.07 Air Entering Condenser Evaporator Air — Ewb (F) (Edb) 62 67 72 62 67 72 62 67 72 62 67 72 — 243 268 — 250 271 236 253 277 238 262 287 TC 75 — 140 110 — 153 120 203 167 126 215 181 136 SHC — 14.8 15.5 — 14.9 15.2 15.7 16.0 15.3 15.7 16.4 17.
GLYCOL HEATING PERFORMANCE GLYCOL COIL (50HJ015-025) Temperature Entering Condenser Edb 55 70 80 Ewt 200 180 160 200 180 160 200 180 160 4400 Cap 310 255 200 274 218 164 249 194 140 25 Gpm 33 27 21 29 23 17 26 21 15 Ldb 120 108 97 127 116 104 132 121 109 Cap 293 237 181 257 201 146 233 177 123 50 Gpm 33 27 21 29 23 17 27 20 14 Ldb 116 105 93 124 112 100 129 117 106 Air Entering Evaporator — Cfm 5400 Percent Glycol 25 50 Cap Gpm Ldb Cap Gpm Ldb 347 37 115 327 37 111 285 30 104 264 30 101 223 24 94
Performance data (cont) FAN PERFORMANCE — 48HJ015-025 UNITS 48HJD015 WITH STANDARD MOTOR (Low Heat Units) Available External Static Pressure (in. wg) Cfm 0.2 0.4 0.6 0.8 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts 753 915 1.05 838 1066 1.23 945 1278 1.47 1044 1500 3750 755 991 1.14 865 1198 1.38 968 1414 1.63 1063 1639 4000 788 1129 1.30 894 1341 1.54 992 1562 1.80 1084 1791 4250 822 1280 1.47 923 1497 1.72 1017 1722 1.98 1106 1956 4500 857 1443 1.66 953 1666 1.92 1044 1896 2.
FAN PERFORMANCE — 48HJ015-025 UNITS (cont) 48HJD015 WITH OPTIONAL MOTOR (Low Heat Units) Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 1.25 945 1298 1.49 1044 1513 1.41 968 1433 1.65 1063 1652 1.57 992 1581 1.82 1084 1803 1.75 1017 1740 2.00 1106 1966 1.94 1044 1912 2.20 1130 2141 2.15 1071 2097 2.41 1154 2329 2.37 1099 2295 2.64 1180 2530 2.61 1129 2506 2.88 1207 2745 2.87 1159 2730 3.14 1234 2973 3.14 1189 2969 3.41 1262 3215 Bhp 1.74 1.90 2.07 2.26 2.46 2.68 2.91 3.
Performance data (cont) FAN PERFORMANCE — 48HJ015-025 UNITS (cont) 48HJD017 (Low Heat Units) Cfm 4500 4800 5100 5700 6000 6300 6600 6900 7200 7500 Rpm 753 747 741 810 844 879 915 950 986 1022 0.2 Watts 1307 1384 1465 1911 2164 2439 2737 3057 3401 3770 Bhp 1.53 1.62 1.72 2.24 2.54 2.86 3.21 3.59 3.99 4.42 Rpm 761 790 820 882 914 947 980 1013 1047 1081 0.4 Watts 1330 1515 1718 2182 2444 2729 3035 3364 3717 4095 Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 1.
FAN PERFORMANCE — 48HJ015-025 UNITS (cont) 48HJD025 (Low Heat Units) Cfm 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 824 881 939 998 1056 1116 1175 1235 1295 0.2 Watts 2607 3030 3488 3982 4512 5077 5678 6315 6988 Bhp 3.09 3.59 4.14 4.72 5.35 6.02 6.74 7.49 8.29 Rpm 894 947 1001 1055 1111 1167 1224 1282 1340 0.4 Watts 2844 3266 3725 4218 4748 5314 5915 6552 7225 Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 3.37 961 3085 3.66 1023 3330 3.88 1009 3507 4.
Performance data (cont) FAN PERFORMANCE — 48HJ015-025 UNITS (cont) 48HJF015 WITH STANDARD MOTOR (High Heat Units) Available External Static Pressure (in. wg) Cfm 0.2 0.4 0.6 0.8 Rpm Watts Bhp Rpm Watts Bhp Rpm Watts Bhp Rpm Watts 753 915 1.05 844 1077 1.24 949 1287 1.48 1047 1507 3750 764 1006 1.16 872 1211 1.39 972 1425 1.64 1067 1648 4000 798 1147 1.32 901 1357 1.56 997 1576 1.81 1089 1803 4250 832 1301 1.50 931 1516 1.74 1024 1739 2.00 1112 1970 4500 868 1467 1.69 962 1688 1.94 1051 1916 2.
FAN PERFORMANCE — 48HJ015-025 UNITS (cont) 48HJF015 WITH OPTIONAL MOTOR (High Heat Units) Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 1.27 949 1306 1.50 1047 1520 1.42 972 1444 1.66 1067 1661 1.59 997 1594 1.83 1089 1814 1.77 1024 1757 2.02 1112 1980 1.97 1051 1932 2.22 1136 2158 2.18 1079 2120 2.44 1161 2350 2.41 1109 2321 2.67 1188 2554 2.65 1139 2536 2.92 1215 2773 2.91 1170 2765 3.18 1244 3005 3.18 1201 3008 3.46 1273 3252 Bhp 1.75 1.91 2.09 2.28 2.48 2.70 2.94 3.
Performance data (cont) FAN PERFORMANCE — 48HJ015-025 UNITS (cont) 48HJF017 (High Heat Units) Cfm 4500 4800 5100 5700 6000 6300 6600 6900 7200 7500 Rpm 753 747 775 849 886 924 962 1000 1038 1077 0.2 Watts 1307 1384 1571 2054 2329 2628 2951 3298 3672 4072 Bhp 1.53 1.62 1.84 2.41 2.73 3.08 3.46 3.87 4.31 4.78 Rpm 786 818 850 918 952 987 1023 1059 1095 1131 0.4 Watts 1404 1603 1822 2323 2607 2915 3246 3603 3986 4394 Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 1.
FAN PERFORMANCE — 48HJ015-025 UNITS (cont) 48HJF025 (High Heat Units) Cfm 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 868 929 991 1054 1117 1180 1244 1308 1372 0.2 Watts 2752 3201 3687 4211 4773 5373 6011 6687 7401 Bhp 3.26 3.80 4.37 5.00 5.66 6.37 7.13 7.93 8.78 Rpm 934 991 1049 1109 1168 1229 1290 1352 1414 0.4 Watts 2987 3436 3923 4447 5009 5609 6247 6924 7638 Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 3.54 997 3227 3.83 1058 3470 4.
Performance data (cont) FAN PERFORMANCE — 50HJ015-025 UNITS 50HJ015 WITH STANDARD MOTOR Cfm 3750 4000 4250 4500 4750 5000 5250 5500 5750 6000 6250 Rpm 753 747 741 761 792 823 855 887 920 953 986 0.2 Watts 915 977 1041 1158 1305 1464 1635 1819 2016 2226 2449 Bhp 1.05 1.12 1.20 1.33 1.50 1.68 1.88 2.09 2.32 2.56 2.82 Rpm 786 810 835 861 887 915 943 972 1002 1031 1062 0.4 Watts 972 1090 1220 1360 1512 1676 1852 2041 2242 2457 2685 Available External Static Pressure (in. wg) 0.6 0.
FAN PERFORMANCE — 50HJ015-025 UNITS (cont) 50HJ015 WITH OPTIONAL MOTOR Cfm 3750 4000 4250 4500 4750 5000 5250 5500 5750 6000 6250 Rpm 753 747 741 761 792 823 855 887 920 953 986 0.2 Watts 942 1006 1073 1191 1339 1499 1671 1854 2050 2258 2480 Bhp 1.08 1.16 1.23 1.37 1.54 1.72 1.92 2.13 2.36 2.60 2.85 Rpm 786 810 835 861 887 915 943 972 1002 1031 1062 0.4 Watts 998 1118 1248 1389 1541 1705 1880 2068 2268 2480 2706 Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 1.
Performance data (cont) FAN PERFORMANCE — 50HJ015-025 UNITS (cont) 50HJ017 Cfm 4500 4800 5100 5700 6000 6300 6600 6900 7200 7500 Rpm 753 747 741 735 759 790 821 852 883 914 0.2 Watts 1307 1384 1465 1659 1854 2088 2340 2611 2903 3215 Bhp 1.53 1.62 1.72 1.95 2.18 2.45 2.74 3.06 3.40 3.77 Rpm 753 747 752 805 832 860 888 917 946 975 0.4 Watts 1307 1384 1500 1895 2118 2360 2621 2900 3200 3521 Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 1.53 784 1397 1.64 859 1635 1.
FAN PERFORMANCE — 50HJ015-025 UNITS (cont) 50HJ025 Cfm 6,000 6,500 7,000 7,500 8,000 8,500 9,000 9,500 10,000 Rpm 753 793 844 895 947 999 1052 1105 1158 0.2 Watts 2385 2738 3151 3596 4073 4583 5125 5699 6306 Bhp 2.83 3.25 3.74 4.27 4.83 5.44 6.08 6.76 7.48 Rpm 816 861 908 955 1004 1053 1103 1153 1204 0.4 Watts 2579 2959 3372 3817 4294 4803 5345 5919 6526 Available External Static Pressure (in. wg) 0.6 0.8 Bhp Rpm Watts Bhp Rpm Watts 3.06 884 2807 3.33 949 3040 3.51 925 3186 3.78 987 3418 4.
Performance data (cont) HORIZONTAL SUPPLY/RETURN FAN PERFORMANCE WITH CRRFCURB013A00 HIGH STATIC REGAIN ADAPTER NOTE: The CRRFCURB013A00 high static regain adapter accessory may be used to provide horizontal supply/return. NOTE: The CRRFCURB013A00 horizontal supply/return adapter accessory improves 48/50HJ015-025 fan performance by increasing external static pressure by amount shown above. To convert from in. wg to Pa use the following formula: in. wg x 249.
ALTITUDE COMPENSATION — 48HJ015-025 (LP Gas Units) LIQUID PROPANE ORIFICE SIZE Low Heat and High Heat 36 37 38 38 39 40 41 41 42 43 ELEVATION (ft) 0-2,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 48/50HJ015-025 COMPONENT Economizer MoistureMi$er Dehumidification Package 4500 0.040 0.045 5000 0.050 0.048 5400 0.060 0.060 6000 0.070 0.071 CFM 7200 0.090 0.103 7500 0.100 0.111 9000 0.110 0.160 10,000 0.120 0.197 11,250 0.140 0.
Performance data (cont) FAN RPM AT MOTOR PULLEY SETTINGS* 48/50HJ 015 (208/230, 460 v)† 015 (208/230, 460 v)** 015 (575 v)† 017† 017** 025† 025** 0 †† †† †† †† †† †† †† 0.
Electrical data ELECTRICAL DATA — 48HJ015-025 UNIT 48HJ COMPRESSOR NOMINAL VOLTAGE OFM IFM RANGE VOLTAGE No. 1 No. 2 (3 Ph, 60 Hz) Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp FLA 208/230 015 (Standard IFM) 015 (Optional IFM) 187 253 20.7 156 19.3 123 3 0.5 1.7 460 414 508 10 70 10 62 3 0.5 0.8 575 518 633 8.2 54.0 7.9 50 3 0.5 0.8 187 253 20.7 156 19.3 123 3 0.5 1.7 414 508 62 3 0.5 0.8 187 253 32.1 195 20.7 156 3 0.5 1.7 460 414 508 16.4 95 10 70 3 0.5 0.
Electrical data (cont) ELECTRICAL DATA — 50HJ015-025 UNIT 48HJ NOMINAL VOLTAGE (3 Ph, 60 Hz) Min Max COMPRESSOR No. 1 No. 2 RLA LRA RLA LRA 208/230 187 253 20.7 156 19.3 460 414 508 10 70 575 518 633 8.2 208/230 187 253 460 414 208/230 VOLTAGE RANGE OFM IFM Qty Hp FLA (ea) Hp FLA 123 3 0.5 1.7 2.9 8.8/ 8.4 10 62 3 0.5 0.8 2.9 4.2 54 7.9 50 3 0.5 0.75 3.0 3.9 20.7 156 19.3 123 3 0.5 1.7 3.7 11.0/ 10.5 508 10 70 10 62 3 0.5 0.8 3.7 4.
LEGEND AND NOTES FOR ELECTRICAL DATA TABLE PAGE 46 FLA HACR IFM LRA MCA MOCP NEC OFM RLA — — — — — — — — — LEGEND Full Load Amps Heating, Air Conditioning and Refrigeration Indoor (Evaporator) Fan Motor Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code Outdoor (Condenser) Fan Motor Rated Load Amps *Heater capacity (kW) is based on heater voltage of 240 v, 480 v, and 575 v. Heaters are rated at 240 v, 480 v, or 575 v.
Typical piping and wiring — 48HJ015-025 (48HJ015 shown) LEGEND NEC — National Electrical Code 48
Typical piping and wiring — 50HJ015-025 (50HJ015 shown) LEGEND NEC — National Electrical Code NOTES: 1. Illustration shown is a general guide only and is not intended to include all details for any specific installation. 2. Installation must comply with all applicable codes. 3. A 90-degree elbow must be installed on the supply duct connection for units equipped with electric heat.
Typical wiring schematic (48HJ017, 208/230 v shown) 50
LEGEND AHA C CAP CB CC CH CLO CLS COMP CR CT DM DU EAS — — — — — — — — — — — — — — EC EMC EQUIP FPT FU GND — — — — — — Adjustable Heat Anticipator Contactor, Compressor Capacitor Circuit Breaker Cooling Compensator Crankcase Heater Compressor Lockout Compressor Lockout Switch Compressor Motor Control Relay Current Transformer Damper Motor Dummy Terminal Economizer Actuator Auxiliary Switch Enthalpy Control Economizer Motor Contactor Equipment Freeze Protection Thermostat Fuse Ground HPS HS HV I IDM IFC
Typical wiring schematic (50HJ017, 208/230 v shown) A B C 52 ELECTRIC HEAT 208/240 v 200/230 v Amps kW 71.3/82.3 25.7/34.2 117/135 42.2/56.1 156/180 56.2/74.
LEGEND AHA BKR W/AT C CAP CB CC CH CLO CLS COMP CR CT DM DU EAS — — — — — — — — — — — — — — — EMC EQUIP FL FPT FU — — — — — Adjustable Heat Anticipator Breaks with Amp Turns Contactor, Compressor Capacitor Circuit Breaker Cooling Compensator Crankcase Heater Compressor Lockout Compressor Lockout Switch Compressor Motor Control Relay Current Transformer Damper Motor Dummy Terminal Economizer Actuator Auxiliary Switch Economizer Motor Contactor Equipment Fuse Link Freeze Protection Thermostat Fuse GND HC
Typical wiring schematic (50HJ017, 208/230 v shown) (cont) NON-FUSED DISCONNECT NOTES: 1. If the non-fused disconnect Service Option is ordered for size 015-025 units, the Non-Fused Disconnect will be factory-installed. 2. The Disconnect takes the place of TB-1 as shown on the unit wiring diagram label and the component arrangement label.
Controls Operating sequence Cooling, units without economizer — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC) and compressor contactor no. 1 (C1) are energized, and evaporator-fan motor (IFM), compressor no. 1 and condenser fan(s) start. The condenser-fan motor(s) runs continuously while unit is cooling. When the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no.
NOTE: When single zone relay pack is used on a VVT Monitor Only System, the monitor thermostat cannot control a damper. *Filter status switch and humidity sensor cannot function simultaneously. Only one sensor can be wired. †Such as a CO2 sensor. **Set auxiliary option to ‘‘ 2’’ — IAQ Control per VTS or VVT Installation Instructions. CO2 COM DX HVAC IAQ LED MIN. NC OAT R. V.
TYPICAL SMOKE CONTROL/FIRE SHUTDOWN WIRING — 48HJ015-025 OPEN ON E CLOSED ON BP OPEN ON BP EAS * EMC CLOSED ON BP,SP,E OPEN ON SD COMPRESSOR WIRING SWITCH CLOSES ON BP,SP,E See Legend on page 51. *Included in power exhaust accessory. NOTE: All switches are field supplied. OPERATING MODES BP — Building Pressurization: E — Evacuation: SD — Complete Unit Shutdown: SP — Smoke Purge: Evaporator fan on, economizer energized to fully open position, power exhaust disabled.
Controls (cont) TYPICAL SMOKE CONTROL/FIRE SHUTDOWN WIRING — 50HJ015-025 LEGEND Field Wiring Field-Supplied Switch See Legend on page 53. *Included in power exhaust accessory. OPERATING MODES BP — Building Pressurization: E — Evacuation: SD — Complete Unit Shutdown: SP — Smoke Purge: 58 Evaporator fan on, economizer energized to fully open position, power exhaust disabled. Evaporator fan off, economizer energized to fully open position, power exhaust on (open). Breaks 24-v power to the thermostat.
TEMP systems A TEMP System is a network of communicating Carrier TEMP System Thermostats and rooftop, factory-mounted Apollo direct digital controls, each serving its own zone and heating/cooling unit. Networking allows your building manager to easily access each of your systems from a single location...whether they are in the same building or located throughout town.
Controls (cont) Variable Volume/Variable Temperature VVT® Systems VVT Systems are dedicated to total building comfort. Carrier thermostats, zone dampers, and HVAC equipment with factory-mounted direct digital controls continually monitor and adjust their operation to ensure uninterrupted and personalized comfort for all occupants.
VVT® application guidelines The installer is responsible for ensuring that the bypass controller is configured and the system is balanced so that the minimum airflow is higher than 300 cfm/ton. To accomplish proper configuration set the System Setup Enable Function (Category 5, option 7) to ON. This will close the bypass damper and force all of the zone dampers to open.
Controls (cont) If the diversity within the space does not vary much, then bypass can be installed as shown in the diagram below successfully. Care must be taken to ensure that maximum bypass air at part load conditions does not exceed 25% of the full load airflow. The bypass junction must be installed with sufficient duct length between it and the unit to allow complete mixing of the bypass air an the return air.
Monitor thermostat configuration — The monitor thermostat controls the operation of its own zone and of each associated zone controller. The monitor thermostat determines system operation from the information received from each device that it controls. The monitor thermostat must be configured for proper control of the system. Part of the configuration is Category 4.0, which deals with HVAC settings. The Category 4.0 HVAC Equipment table shows the default settings for this category.
Application data Ductwork Minimum temperature (48HJ015-025 only) Ductwork should be attached to the curb on all units. Interior installation may proceed before unit is set in place on roof. If ductwork will be attached to the unit, do not drill in condensate drain pan area — leaks may result. See figures on page 65 for information on field-installed concentric ductwork when applicable. Air entering the heat exchanger in heating must be a minimum of 50 F (10 C) continuous and 45 F (7.2 C) intermittent.
CONCENTRIC DUCT DETAILS CONCENTRIC DUCT AIR DISTRIBUTION 6'-2 3/8'' MAX. 5'-9 3/16'' MAX. 1'-10 11/16'' MAX. 5 3/16'' 4'-6 13/16'' 1'-0 3/16'' 1'-7 15/16'' 1'-0 3/16'' B B 24'' MIN. A A BAFFLE NOTE: Do not drill in this area, damage to basepan may result in water leak. Shaded area indicates block-off panels. NOTE: Dimensions A, A′ and B, B′ are obtained from field-supplied ceiling diffuser. Concentric ducts may only be installed on units without electric heat.
Application data (cont) Applications — There are many different rooftop unit applications that are susceptible to problems caused by high humidity levels. Some common applications include: • Restaurants: The kitchen areas of restaurants have many humidity producing activities such as dish washing and cooking. • Supermarkets: High humidity levels cause inefficiency in operation of refrigeration and freezer systems. • Museums and Libraries: Humidity can damage books and artwork.
NOTE: Numbers 1 through 4 indicate point numbers referred to in MoistureMi$er Dehumidification Package Design Effects section.
LEGEND db — Dry Bulb wb — Wet Bulb Point 1 — Entering Air (F) 80 db/67 wb Point 2 — Leaving Air (F) 58.9 db/56.4 wb (Without Subcooler) Point 3 — Leaving Air (F) 63.0 db/56.
Guide specifications — 48/50HJ015-025 Packaged Rooftop Electric Cooling Unit with Gas, Electric, or Glycol Heat — Constant Volume Application HVAC Guide Specifications Size Range: 12 to 20 Tons, Nominal (Cooling) 172,000 to 360,000 Btuh, Nominal (Input Heating) (Gas Units) 14 to 80 kW (Electric Heat) 123,000 to 405,000 Btuh (Glycol Heating) Carrier Model Numbers: 48HJD, 48HJF 50HJ Part 1 — General 1.
Guide specifications — 48/50HJ015-025 (cont) 4. All compressors shall have 70 W crankcase heaters. E. Coils: 1. Standard evaporator and condenser coils shall have copper or aluminum plate fins mechanically bonded to seamless internally grooved copper tubes with all joints brazed. 2. Coils shall be leak tested at 150 psig (1034 kPa) and pressure tested at 450 psig (3103 kPa). 3.
2. Safeties: a. Unit shall incorporate a solid-state compressor lockout which provides reset capability at the space thermostat, should any of the following safety devices trip and shut off compressor: 1) Compressor lockout protection provided for either internal or external overload. 2) Low-pressure switch. 3) Dual freezestats (evaporator coil). 4) High-pressure switch. b. Supply-air thermostat shall be located in the unit. c.
Guide specifications — 48/50HJ015-025 (cont) * 7. Thermostats and Subbases: To provide staged heating and cooling in addition to automatic (or manual) changeover and fan control. * 8. Barometric Relief Damper Package: a. Package shall include damper, seals, hardware, and hoods to relieve excess internal pressure. b. Damper shall close due to gravity upon unit shutdown. c. Damper package must be field-installed in return-air ductwork when used with optional side return connections. * 9.
c. Heater assemblies are provided with integral fusing for protection of internal heater circuits not exceeding 48 amps each. d. Auto reset thermo limit controls, magnetic heater contactors (24 v coil) and terminal block all mounted in electric heater control box (minimum 18 ga. Galvanized steel) attached to end of heater assembly. e.
Carrier Corporation • Syracuse, New York 13221 5-00 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. 1 Book 1 1 4 4 New Book 1 Pg 76 Catalog No. 524-809 Printed in U.S.A.