Operating instructions
GALAXY 11
2. Continuous Burning Pilot (24V).
FOR BOILERS EQUIPPED WITH HONEYWELL GAS VALVE
VR8200, VR8300, V8200 or V800. (see figures 10 and 11).
A. This appliance has a pilot which must be lighted by hand. When
lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas.
Be sure to smell next to the floor because some gas is heavier
than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in
your building.
• Immediately call your gas supplier from a neighbor's phone.
Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob.
NEVER use tools. If the knob will not push in or turn by hand,
DON'T try to repair it, call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
D. DO NOT use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and any
gas control which has been under water.
Lighting Instructions
1.STOP! Read the safety information on this page.
2.Set the thermostat to lowest setting.
3.Turn off all electric power to the appliance.
4.Remove control access panel.
5. Push in gas control knob slightly and turn clockwise 
to "OFF".
6. Wait five (5) minutes (longer for propane) to clear out any
gas, then smell for gas, including near the floor. If you then
smell gas, STOP! Follow "B" in the safety information on
this page. If you don't smell gas, go to next step.
7. Remove the 
base burner 
access panel located below and
behind the gas control unit.
8. Find pilot—follow metal tube from gas control. The pilot is
between two burner tubes behind the burner access
panel.
9. Turn knob on gas control counterclockwise to "PILOT".
10. Push in red button all the way and hold in. Immediately
light the pilot with a match. Continue to hold the red but-
ton in for about one (1) minute after the pilot is lit. Release
knob and it will pop back up. Pilot should remain lit. If it
goes out, repeat steps 5 through 10.
– If knob does not pop up when released, stop and imme-
diately call your service technician or gas supplier.
– If the pilot will not stay lit after several tries, turn the gas
control knob to “OFF” and call your service technician or
gas supplier.
11. Replace 
base burner 
access panel.
12. Turn gas control knob counterclockwise to "ON".
13. Replace control access panel
14. Turn on all electric power to the appliance.
15. Set thermostat to desired settings.
To Turn Off Gas To Appliance
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be
performed.
3. Remove control access panel.
4. Turn gas control knob clockwise to "OFF". DO NOT
force.
5. Replace control access panel.
3: WHITE RODGERS IID SYSTEM FOR NATURAL GAS ONLY.
FOR BOILERS EQUIPPED WITH GAS VALVE 36C84 (see
figure 12)
A.  This appliance is equipped with an ignition device which auto-
matically lights the pilot Do not try to light the pilot by hand.
B.  BEFORE OPERATING smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand,
don’t try to repair it, call a qualified service technician. Force
or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and
any gas control which has been under water.
SAFETY INFORMATION
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, 
a fire or explosion may result causing property damage, per-
sonal injury or loss of life.
SAFETY INFORMATION
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, 
a fire or explosion may result causing property damage, per-
sonal injury or loss of life.
Figure 11.
Figure 10. Valve VR8200, VR8300, V8200 or V800